6.4.1- Compressor faults 6.4.1.1 - General
Each compressor is protected against multiple faults by two digital inputs located on the control board. If one of these inputs opens, it causes an immediate shutdown on the compressor without any action from the basic board.
6.4.1.2 - Compressor protection devices
On
ALARM CODE DESCRIPTIONS
DGT (only for units with low-temperature option):
The discharge gas thermostat detects and protects the compressor against abnormally high discharge temperatures.
Starter Guard:
This board patented by Carrier (also called AM board) monitors both the compressor regime and the status of its crankcase heaters which ensure correct lubrication when the compressor starts.
Code | Alarm name | Action | Pumpdown | Reset type | Probable cause |
101 | DGT fault, compressor A1 | Circuit A shut down | No | Manual | Hot gas thermostat contact open |
102 | Starter Guard fault compressor A1 | Circuit A shut down | No | Ditto | Crankcase heater fault and open motor current |
|
|
|
|
| fault detection board contact |
201 | DGT fault, compressor A2 | Compressor A2 shut down |
| Ditto | Hot gas thermostat contact open |
202 | Starter Guard fault compressor A 2 | Compressor A2 shut down |
| Ditto | Crankcase heater fault and open motor current |
|
|
|
|
| fault detection board contact |
301 | DGT fault, compressor A3 | Compressor A3 shut down |
| Ditto | Hot gas thermostat contact open |
302 | Starter Guard fault compressor A 3 | Compressor A3 shut down |
| Ditto | Crankcase heater fault and open motor current |
|
|
|
|
| fault detection board contact |
401 | DGT fault, compressor A4 | Compressor A4 shut down |
| Ditto | Hot gas thermostat contact open |
402 | Starter Guard fault compressor A 4 | Compressor A4 shut down |
| Ditto | Crankcase heater fault and open motor current |
|
|
|
|
| fault detection board contact |
501 | DGT fault, compressor B1 | Circuit B shut down | No | Ditto | Hot gas thermostat contact open |
502 | Starter Guard fault compressor B1 | Circuit B shut down | No | Ditto | Crankcase heater fault and open motor current |
|
|
|
|
| fault detection board contact |
601 | DGT fault, compressor B2 | Compressor B2 shut down |
| Ditto | Hot gas thermostat contact open |
602 | Starter Guard fault compressor B 2 | Compressor B2 shut down |
| Ditto | Crankcase heater fault and open motor current |
|
|
|
|
| fault detection board contact |
701 | DGT fault, compressor B3 | Compressor B3 shut down |
| Ditto | Hot gas thermostat contact open |
702 | Starter Guard fault compressor B3 | Compressor B3 shut down |
| Ditto | Crankcase heater fault and open motor current |
|
|
|
|
| fault detection board contact |
801 | DGT fault, compressor B4 | Compressor B4 shut down |
| Ditto | Hot gas thermostat contact open |
802 | Starter Guard fault compressor B4 | Compressor B4 shut down |
| Ditto | Crankcase heater fault and open motor current |
|
|
|
|
| fault detection board contact |