7-3. AUTO RESTART FUNCTION

When the indoor unit is controlled with the remote controller, the operation mode, the set temperature, and the fan speed are memorized by the indoor electronic control P.C. board. The “AUTO RESTART FUNCTION” sets to work the moment power has restored after power failure. Then, the unit will restart automatically.

Operation

1If the main power has been cut, the operation settings remain.

2After the power is restored, the unit restarts automatically according to the memory.

(However, it takes at least 3 minutes for the compressor to start running.)

How to release “AUTO RESTART FUNCTION” 1Turn off the main power of the unit.

2Solder the Jumper wire JR07 on the indoor electronic control P.C. board. (Refer to 8-7.)

MSZ-A09/12/15/17NA

MSZ-A24NA

MSY-A15/17NA

MSY-A24NA

CN211

 

CN211

JR07

BZ

CN151 CN112

JR07

BZ

CN152

CN101

CN151 CN112

NOTE:

The operation settings are memorized when 10 seconds have passed after the indoor unit was operated with the remote controller.

If main power is turned OFF or a power failure occurs while AUTO START/STOP timer is active, the timer setting is cancelled.

If the unit has been off with the remote controller before power failure, the auto restart function does not work as the power button of the remote controller is off.

To prevent breaker off due to the rush of starting current, systematize other home appliance not to turn on at the same time.

When some air conditioners are connected to the same supply system, if they are operated before power failure, the starting current of all the compressors may flow simultaneously at restart.

Therefore, the special counter-measures are required to prevent the main voltage-drop or the rush of the starting current by adding to the system that allows the units to start one by one.

8

TROUBLESHOOTING

MSZ-A09NA MSZ-A12NA MSZ-A15NA MSZ-A17NA MSZ-A24NA MSY-A15NA MSY-A17NA MSY-A24NA

8-1. Cautions on troubleshooting

1.Before troubleshooting, check the following

1)Check the power supply voltage.

2)Check the indoor/outdoor connecting wire for mis-wiring.

2.Take care of the following during servicing

1)Before servicing the air conditioner, be sure to turn off the unit first with the remote controller, and then after confirming the horizontal vane is closed, turn off the breaker and / or disconnect the power plug.

2)Be sure to turn OFF the power supply before removing the front panel, the cabinet, the top panel, and the electronic control P.C. board.

3)When removing the electronic control P.C. board, hold the edge of the board with care NOT to apply stress on the components.

4)When connecting or disconnecting the connectors, hold the housing of the connector. DO NOT pull the lead wires.

Lead wiring

Housing point

11

Image 11 Contents
Revised EDITION-B ContentsTechnical Changes Part Names and Functions Specification Outlet AIR Speed and Coverage Range Operating RangeUnit inch Outlines and DimensionsMSZ-A09NA MSY-A15NA MSZ-A12NA MSY-A17NA MSZ-A15NA MSZ-A17NA MSZ-A24NA Wiring Diagram MSZ-A17NA MSY-A17NA Refrigerant System DiagramMSZ-A09NA MSZ-A12NA MSZ-A15NA MSY-A15NAP.C. Board Modification for Individual Operation Service FunctionsTimer Short Mode How to modify the remote controller P.C. boardOperation TroubleshootingAuto Restart Function Outdoor Unit MXZ series Troubleshooting procedureHow to replace batteries Information for Multi System AIR ConditionerThose figures show about MSZ-A09/12/15/17 Failure mode recall functionIndoor unit failure mode table Operation Instruction of troubleshootingIndicates abnormalities Troubleshooting check tableMXZ type Trouble criterion of main partsCheck of indoor fan motor Troubleshooting flowCheck of remote controller and receiver P.C. board Indoor electronic control P.C.Board How to check mis-wiring and serial signal error Electromagnetic noise enters into TV sets or radios Board Test point diagram and voltagePower monitor receiver P.C Indoor electronic control P.C. boardDisplay P.C. board Receiver Board MSZ-A24NA MSY-24NAMSZ-A09/12/15/17NA MSY-A15/17NA Disassembly InstructionsRemoving the panel Photo Photo Removing the electrical box Operating Procedure PhotosMotor band Removing the horizontal vane motor unit PhotoRemoving the indoor fan motor and the line flow Photo FanBoard and the display P.C. board MSZ-A24NA MSY-A24NA Operating Procedure PhotosRemoving the front panel Removing the electronic control P.C. board, the receiverRemoving the line flow fan and the indoor fan motor Removing the vane motorAccessory and Remote Controller Parts ListSleeve Bearing Nozzle AssemblySwitch Holder Bearing MountAIR Cleaning Filter ANTI-ALLERGY Enzyme Filter Grille Front Panel AssemblyCatch Screw CAPIndoor Unit Functional Parts and Electrical Parts AIR Cleaning Filter ANTI-ALLERGY Enzyme Filter Remote Controller KM07J Remote Controller KM07LE12 897 702 Qty/unit RoHSE12 751 509 E12 001 504E12 A56 RoHS Part name E12 A5411 G E12 A58 620 Indoor Heat Exchanger 4PCS/ SET3PCS/ SET 11 G E12 408 303 Vane Motor Horizontal E12 A58 300 Indoor FAN Motor Assembly W1Remote Controller KM07K Remote Controller KM07MAIR Cleaning Filter ANTI-ALLERGY Enzyme Filter Indoor Unit Display Section Microprocessor ControlFAN d Operation MSY Cool OperationDRY Operation Heat Operation MSZFuzzy control Auto Change Over ··· Auto Mode Operation MSZMode selection Upward Auto Vane OperationMSZ-A09/12/15/17 MSY-A15/17 MSZ-A24 MSY-A24COOL/DRY Heat 3 4 Swing 5Program Timer Timer OperationMade in Japan Changing temperature indication F/CEMERGENCY/TEST Operation MSZ-ANA MSY-ANA