USER MENU

USER MENU OPERATION SETTINGS:

The control has user Menu settings that will determine how the control operates. The unit is shipped with factory de- fault settings. The user must change any of the settings as required for the application. To reset all settings to factory

defaults, press and hold all 3 buttons simultaneously (, , and buttons) for approximately 5 seconds.

To view Menu items, press and hold for 5 seconds. The unit will display the first Menu item on the left side of the display. The right side of the display indicates the Menu item settings. To change the setting, momentarily press the or key.

A momentary press of the key advances the display to the next Menu item, and continues, till the last menu item is displayed. Pressing the key one more time with the last menu item, (aL) displayed returns the control to the operating mode.

Each press of results in forward movement to the next Menu item. If you need to change an item “passed”, you

must repeatedly press , return to the operating mode,

then press and hold for 5 seconds to re-enter the Menu

mode. Then repeatedly, momentarily press until the desired Menu item is again displayed.

To store any changes made to any Menu items, the Menu

must be exited by pressing when the last item is displayed. If no buttons are pressed for ten minutes while in the menu, the control will return to operating mode and any changes that were made will be lost.

The following table shows the menu items, default settings and optional settings.

NOTE: The Heat/ Cool switch (SW1) MUST be in the proper position BEFORE setting options.

 

 

 

Options

 

Menu

 

Factory

Press

 

 

or

Comments

 

 

 

 

 

 

 

 

Item

Description

Default

to select

CF

Temperature Scale

F

C or F

Selects temperature display in Fahrenheit or Celsius

 

 

 

 

 

 

 

 

dFF

Differential

5

1 to 30

Selects the range between Cut In and Cut Out.

 

 

 

 

 

 

 

 

SP

Set Point Mode

Cl

CO or CI

Selects how the set point temperature will operate the

 

Cool

CO

CI or CO

load terminal. CI indicates the setpoint temperature

 

Heat

 

 

 

 

 

will be the Cut In temperature. CO indicates the

 

 

 

 

 

 

 

temperature will be the Cut Out temperature. See

 

 

 

 

 

 

 

Operation section.

 

 

 

 

 

 

 

 

SOF

Sensor Operation Failure

1

0 or 1

Cooling - Selects the operation of the Control Load

 

Cool

0

None

relay in the event of a sensor failure in Cool mode. 1

 

Heat

 

 

 

 

 

(default) will cause the load contacts of the relay to

 

 

 

 

 

 

 

close and remain closed if the sensor either opens or

 

 

 

 

 

 

 

shorts. 0 causes the load contacts of the relay to open

 

 

 

 

 

 

 

and remain open.

 

 

 

 

 

 

 

Heating has no optional selection. Sensor failure

 

 

 

 

 

 

 

in Heating will result in the relay contacts opening.

 

 

 

 

 

 

 

 

dL

Display Light

Off

On or Off

Selects the LCD display light Off or On. With this

 

 

 

 

 

 

 

selected Off, the display light will illuminate any time a

 

 

 

 

 

 

 

keypad button is pressed to provide better viewing in

 

 

 

 

 

 

 

low lighting conditions, and go off after 10 seconds. If

 

 

 

 

 

 

 

On is selected, the display light will be On continuously.

 

 

 

 

 

 

 

 

ASd

Anti Short-Cycle Delay

Cool

0 to 12

Selects the minimum time (in minutes) that the load

 

 

1

 

 

 

 

contacts will remain open after a cycle before closing

 

 

 

 

 

 

 

again. This will prevent the compressor or other load

 

 

Heat

 

 

 

 

from being damaged by cycling too soon. A blinking

 

 

0

 

 

 

 

Snowflake or Flame icon indicates that the control has

 

 

 

 

 

 

 

a demand to energize the load, but is waiting for the

 

 

 

 

 

 

 

delay time to elapse. A setting of 0 indicates no time

 

 

 

 

 

 

 

and the feature is disabled. SW1 must be set to the

 

 

 

 

 

 

 

proper position before checking this setting.

 

 

 

 

 

 

 

 

LP

Lock Front Panel Keypad

Off

On or Off

When selected Off, the keypad can be used as normal.

 

 

 

 

 

 

 

When selected On, prevents unauthorized access to

 

 

 

 

 

 

 

the control settings by locking out all keys. To unlock

 

 

 

 

 

 

 

the control when it is locked, press and hold the Menu

 

 

 

 

 

 

 

key for 5 seconds.

 

 

 

 

 

 

 

 

OFS

Ambient Temperature

0

-4, -3, -2, -1, 0,

This control is calibrated at the factory, but the “sensed"

 

Offset

 

1, 2, 3, 4

temperature may read different because of mount-

 

 

 

 

 

 

 

ing/installation, or other factors. This item allows the

 

 

 

 

 

 

 

displayed temperature to be shifted the number of

 

 

 

 

 

 

 

degrees set to compensate for this difference

 

 

 

 

 

 

 

 

4

Image 4
Contents Precautions DescriptionInstallation Green Status Indicator LED and display backlight operationCircuit Board Inside Cover SW1Wiring SW2Options Menu Factory Press Comments Description Default User Menu Operation SettingsUser Menu Operation COOL/REFRIGERATIONLock Panel LP Specifications NTC Temperature Versus Resistance TablesPTC Temperature Versus Resistance Tables NTCTroubleshooting Problemas DE Solución Especificaciones Alarma de salida de combinado Uso FuncionamientoUsuario DEL Funcionamiento Usuario DEL MenúMás Referencia de Diferencial De operativo Temperatura RangoFrontal panel del Off u On Teclado BloquearCalor 12 a Frío Corto ciclo-anti Demora ASdEléctricas Conexiones Instalación 6857G-37 Pieza DE N Opcionales servicio de Accesorios/Elementos 10-16E09

16E09-101 specifications

The Emerson 16E09-101 is a cutting-edge electronic controller designed specifically for heating, ventilation, and air conditioning (HVAC) systems. This controller stands out due to its advanced features, technologies, and characteristics that facilitate enhanced control and efficiency in managing climate conditions in both residential and commercial environments.

One of the main features of the 16E09-101 is its ability to support multiple HVAC components, including heat pumps, air conditioners, and ventilation systems. This versatility makes it suitable for a variety of applications. The controller is equipped with a user-friendly interface, which simplifies the setup process and allows users to monitor and adjust settings easily. The graphical display presents real-time data, including temperature, humidity, and system status, enabling quick diagnosis and troubleshooting of issues.

The Emerson 16E09-101 incorporates sophisticated control algorithms that optimize system performance while minimizing energy consumption. By utilizing advanced predictive logic, the controller can make adjustments to the operation of HVAC units based on real-time data inputs. This not only increases energy efficiency but also prolongs the lifespan of the equipment, offering cost savings over time.

Another key characteristic of the 16E09-101 is its built-in communication capabilities, which facilitate integration with building management systems (BMS). This feature enables centralized control and monitoring, allowing facility managers to oversee multiple units from a single interface. Additionally, its compatibility with various communication protocols ensures that it can easily connect to existing systems, further enhancing its utility.

The controller also supports a range of sensors, including temperature, humidity, and CO2 sensors, allowing for comprehensive monitoring of indoor air quality. This is particularly important in modern buildings where energy conservation must be balanced with occupant comfort.

In summary, the Emerson 16E09-101 is a highly capable and versatile electronic controller ideal for managing HVAC systems efficiently. With its advanced features, proactive control technologies, and robust communication capabilities, it offers significant benefits in terms of energy efficiency, system longevity, and user convenience. Whether for residential or commercial applications, the 16E09-101 exemplifies Emerson's commitment to innovation and quality in HVAC control solutions.