Jenn-Air JXT8136ADS, JXT8142ADS specifications INSTALLATION3, Mounting Heights & Clearance, Ducting

Page 4

INSTALLATION3

MOUNTING HEIGHTS & CLEARANCE

29"-46.65"

5.31"

Min 24"-Max 32"

*Min 89.94"

*Max 113.71"

36"

DUCTING

A minimum of 6" round or 3-1/4” x 10"rectangular duct must be used to maintain maximum air flow efficiency.

Always use rigid-type metal ducts only.

Flexible ducts could restrict air flow by up to 50%.

Also use calculation (on right) to compute total available duct run when using elbows, transitions and caps.

ALWAYS, when possible, reduce the number of transitions and turns. If long duct run is required, increase duct size from 6" to 7 or 8". If a reducer is used, install a long reducer instead of a pancake reducer. Reduce duct size as far away from open- ing as possible.

If turns or transitions are required:

Install as far away from opening and as far apart, between 2, as possible.

Minimum mounting height between range top to hood bottom should be no less than 24".

Maximum mounting height should be no higher than 32".

It is important to install the hood at the

proper mounting height. Hoods mounted too low could result in heat damage and fire hazard; while hoods mounted too high will be hard to reach and will lose performance and efficiency.

If available, also refer to range manufacturer's height clearance requirements and recommend- ed hood mounting height above range.

Extension kits available to accommodate 10’-12’ ceilings.

*Minimum ceiling clearance 89.94” at 24” hood mounting height.

**Maximum ceiling clearance 113.71" at 32" hood mounting height.

Minimum Duct Size:

Round- 6" minimum

Rectangular-requires an adaptor readily available at most hardware stores.

Duct Run Calculation:

Maximum run

6" or 3-1/4” x 10" duct

100

FT

Calculated Length:

 

 

each 90 Elbow used

15

FT

each 45 elbow used

9

FT

each 6" to 3/14 x 10"

 

 

transition used

1

FT

each 3/14 x 10" to 6"

 

 

transition used

5

FT

Side Wall Cap w/ damper

30

FT

Roof Cap

30

FT

 

 

 

e.g.- 1 roof cap, 2x90 elbows, 1 45 elbow used:

=30' + 30' + 9' =69' used, 31' available for straight duct runs.

Image 4
Contents Installation Installation Guide Important Safety NoticeList of Materials INSTALLATION3 Mounting Heights & ClearanceDucting If turns or transitions are requiredINSTALLATION4 Specifications Electrical INSTALLATION5Cable Lock INSTALLATION6 InstallationINSTALLATION7 Push telescopic duct section up in place and fastenINSTALLATION8 Ductless ConversionHotte DE Cuisinière Guide D’INSTALLATION Avis DE Sécurité ImportantListe DES Matériaux Hauteurs DE Montage ET Dégagement CanalisationAvertissement DE Risque D’INCENDIE Avertissement Caractéristiques Techniques Électricité AvertissementApposé sur le produit Verrou de câble Attachez le conduit au plafond et les composants élétriques Crochets de montage locking tabs Réinstallez les filtres métalliques Transformation EN Système DE RecyclageFiltres au charbon requis Retirez les filtres métalliques de la hotteInstalacion Guia DE Instalacion Iimportante Aviso DE SeguridadLista DE Materiales Altura DE Montado Y Espacio Libre INSTALACION3Tuberia DE Extraccion INSTALACION4 Advertencia Peligro DE IncendioINSTALACION5 Especificaciones Instalacion ElectricaAdvertencia Seguro de CableINSTALACION6 INSTALACION7 Cambiará de ,Exhaust Mode modo de INSTALACION8Conversion SIN Tuberia DE Extraccion Vuelva a instalar los filtros de metal