UTILITY
WARNING
DO NOT USE CONDUIT FOR GROUND CONNECTION.
CAUTION
IT IS RECOMMENDED THAT THE OVEN BE PLACED UNDER A VENTILATION HOOD FOR ADEQUATE AIR SUPPLY AND VENTILATION.
ELECTRIC SUPPLY TO BE
PROVIDED BY CUSTOMER
CIRCUIT BREAKER
Separate circuit breaker with lockout/tagout electrical shutoff for each oven. Wire each oven separately.
100 Amp circuit breaker for
ELECTRICAL SPECIFICATIONS
DOMESTIC: 208V main blower motors and elements,
3Ph, 75 Amp draw, 50/60 Hz,
3pole, 4 wire system per oven (3 hot, 1 grd).
Do NOT use conduit for ground.
or
DOMESTIC: 240V main blower motors and elements,
3Ph, 65 Amp draw, 50/60 Hz,
3pole, 4 wire system per oven (3 hot, 1 grd).
Do NOT use conduit for ground.
or
EXPORT: 380V elements, 3 Ph, 41 Amp draw, 50/60 Hz,
Do NOT use conduit for ground.
or
DOMESTIC: 480V elements, 3 Ph, 32.5 Amp draw, 50/60 Hz,
Do NOT use conduit for ground.
To Oven
To Oven
Suggested dimensions are shown; utility code requirements supersede any factors shown.
Figure 2-19. Typical PS740-Series Oven(s)
Installation
ELECTRICAL RATING
27.0kW/hr.
SUPPLY WIRE
Supply wire size must be in accordance with the National Electrical Code (current edition) and must be in compliance with local codes.
NOTE: The electrical terminal connection marked “MP” located inside the control compartment is desiganated for the blue (neutral) wire to the oven. See the electrical wiring/schematics in Section 6 of this manual.
SUGGESTED
If space permits, service should be located near the control console end of the oven(s) to allow convenient access to safety switches.
P/N 60254 September 28, 2012 | 18 |