Unified Brands Premier Ventilation specifications Exhaust FAN & Duct

Page 6

Installation Instructions

EXHAUST FAN & DUCT

1. Check all local codes prior to installation.

 

2.All exhaust fans are supplied with a hinge kit and grease box.

3.The exhaust fan curb should be installed directly above the hood if possible. Always maintain the shortest duct run possible.

4.Cut hole and seal exhaust fan curb to roof.

5.Duct shall be sized to provide air velocities not exceeding 1200 FPM.

6.Install hinges and airline cable on exhaust fan cap and metal curb. Remember to leave ample room for fan to tilt back. Fan will remain in tilted back position.

7.Install grease collection box on side of fan that has grease tube discharge.

8.The exhaust duct must be constructed of 16 gauge carbon steel or 18 gauge stainless

steel. All seems must be fluid welded.

9.A duct transition should be provided below exhaust fan inlet.

10.The exhaust duct must be fluid welded to hood collar.

11.Make all necessary electrical connections and check fan for proper rotation.

NOTE: Fan will exhaust air running in wrong direction.

6888-994-7636

Image 6
Contents Operators Manual Notify Carrier of Damage AT OnceTable of Contents Retain this manual for future reference Installation Instructions Types of SystemsCanopies Exhaust FAN & Duct Installation Instructions Control Panel if provided Paws Control PanelInstallation Instructions Side Skirts Fresh AIR Supply FAN See FigTOP Enclosures Installation of Enclosure Panels See Fig Insulated Stainless Steel Wall Panels Start / Check / Balance Direct Draw HoodsMAKE-UP AIR Hoods Exhaust Fans Final Air Balance MAKE-UP AIR HoodsUnified Brands