Final Air Balance

MAKE-UP AIR HOODS

1.

Close all doors and windows.

 

 

 

2.

Operate all exhaust fans even those serving other hoods, supply fans, make-up air

 

 

unit and building HVAC system.

 

3.

Turn on all cooking equipment under the hood and preheat to operating temperature.

 

4.

Produce large quantities of smoke or steam.

 

5.

Observe capture of vapors.

6. If all vapors are not totally captured, ne tune the system by adjusting the air volume control damper installed in the supply collar. Slightly reduce the amount of supply air directed under the hood until full capture is obtained.

UNIFIED BRANDS

1055 Mendell Davis Drive Jackson, MS 39272 888-994-7636 fax 888-864-7636 unifiedbrands.net

Image 12
Contents Operators Manual Notify Carrier of Damage AT OnceTable of Contents Retain this manual for future reference Installation Instructions Types of SystemsCanopies Exhaust FAN & Duct Installation Instructions Control Panel if provided Paws Control PanelInstallation Instructions Side Skirts Fresh AIR Supply FAN See FigTOP Enclosures Installation of Enclosure Panels See Fig Insulated Stainless Steel Wall Panels Start / Check / Balance Direct Draw HoodsMAKE-UP AIR Hoods Exhaust Fans Final Air Balance MAKE-UP AIR HoodsUnified Brands