Cornelius CH951, CH750, CH751 manual Troubleshooting Guide, Operate

Page 8

TROUBLESHOOTING GUIDE

Trouble

 

Probable Cause

 

Remedy

CHILLER DOES NOT

A.

No power.

A.

Check fuse or circuit breaker.

OPERATE

 

 

 

 

 

B.

Loose or poor wire connection.

B.

Check wiring. Correct for loose or

 

 

 

 

poor wire connection.

 

C.

Inoperable ON–OFF switch.

C.

Replace ON–OFF switch.

 

D.

Overload device open.

D.

Allow compressor to cool, then

 

 

 

 

install new overload device;

 

 

 

 

replace compressor if necessary.

 

E.

Inoperable relay.

E.

Replace relay.

 

F.

Low input voltage.

F.

Nominal voltage ± 10% is

 

 

 

 

required.

 

 

 

 

 

NO CIRCULATION OF

A.

Vinyl tubing kinked.

A.

Check tubing and remove kinks.

CHILLED WATER

 

 

 

 

 

B.

Low water level.

B.

Ensure that tank is full.

 

C.

Inoperable pump.

C. Check for obstruction or binding

 

 

 

 

impeller, replace pump and/or

 

 

 

 

motor if necessary.

 

 

 

 

 

INADEQUATE COOLING

A.

Condenser fins dirty.

A.

Blow dirt out of fins.

 

B.

Fan motor not operating freely.

B.

Lubricate and hand spin until fan

 

 

 

 

rotates freely; replace fan blade

 

 

 

 

and/or motor if necessary.

 

C.

Water not circulating

C.

See “NO CIRCULATION OF

 

 

 

 

CHILLED WATER”.

 

D.

Low refrigerant level.

D.

Charge system with refrigerant.

 

E.

Inoperative temperature

E.

Replace thermostat.

 

 

control.

 

 

 

 

 

 

 

6

91272

Image 8
Contents Chiller CH Series Table of Contents List of FiguresSpecifications IntroductionInstallation Instructions START-UP/OPERATIONLocation PlumbingMaintenance ServiceReplacing Switch Removing WrapperReplacing Pump Replacing Electronic Differential ThermostatReplacing FAN Blade AND/OR Motor Fluid Recommendation Commercial/Automotive AntifreezeTroubleshooting Guide OperateParts List NamePage Warranty Remcor Incorporated Regency Drive Glendale Heights, IL