Cornelius WCF1411-A Electrical Checkout, Overload Check, Compressor Check, Capacitor Check

Page 18
FIGURE 9. OVERLOAD CHECK
FIGURE 10. COMPRESSOR CHECK

Continuous Flow Icemaker Service Manual

ELECTRICAL CHECKOUT

1.Be sure the unit is disconnected from the power source. Remove the compressor electrical box cover. Check for obvious damage and loose wires.

2.Disconnect the fan motor leads. Since capacitors store energy, short the capacitor with a screwdriver. This will prevent shocks.

3.Disconnect the compressor terminal wires.

OVERLOAD CHECK

Using a volt–ohmmeter check the continuity across the overload, contact #1 and #3. If none, wait for unit to cool down and try again. If still no continuity, the overload protector is defective and should be replaced.

COMPRESSOR CHECK

The resistance readings on the windings will be between 0.25 to 10.00 ohms, a meter capable of these low readings must be used.

1.Check between “C” and “R.” Replace the compressor if there is no continuity as the run windings are open.

2.Check between “C” and “S.” Replace the

compressor if there is no continuity as the start windings are open.

3.Check between “C” and “R” or “S” and the shell of the compressor. If there is continuity, replace the compressor as the motor is grounded.

4.Check between screw terminal on the overload and “C” on the compressor. Check and repair the lead or connections if there is no continuity.

CAPACITOR CHECK

1.Check or replace start capacitor, disconnect bleed resistor before checking for shorted capacitor.

2.Check or replace run capacitor (if supplied) check for shorted capacitor or either terminal grounded to case.

SAFETY CONTROLS

Your icemaker unit has several safety and control devices incorporated into its design.

WARNING: None of the below described devices should ever be “bypassed” to allow the unit to function.

The safety and control system shut–off devices are:

1.Low water shut off reed switch located in icemaker float assembly. (Automatic reset type.)

2.Gearmotor thermal overload, manual reset type (red button on motor).

3.Compressor thermal overload, automatic reset type.

4.Anti–freeze relay and associated circuit. See wiring diagrams.

5.Main service switch located on top of the control box.

6.Bin Control.

7.High pressure cut out (water cooled only).

Publication Number: 630460324SER

- 14 -

© 2006, IMI Cornelius Inc.

Image 18
Contents Continuous Flow Icemaker Continuous Flow Icemaker Table of Contents Page Safety Tips SafetySafety Instructions Qualified Service Personnel Shipping and StorageSpecification Chart General DescriptionSeries WCC1401-A/WCF1411-A Dimension Drawing Schematic WCC1401-A/WCF1411-A ElectricalRefrigeration Schematic WCC1401-ACleaning and Sanitizing Icemaker Cleaning and Sanitizing ProceduresMaintenance Semi-Annually Pumpdown Cycle Refrigeration System AdjustmentsRefrigeration System Expansion ValveHOW Water Level Control Works To Replace Water Level Safety SwitchWater Level Control Purpose of Water Level ControlBIN Control GearmotorGearmotor Overload Tripped To Replace Gearmotor Assembly Motor CheckStart Relay Installation and Shaft Seal Replacement Upper NUT and Bearing AssemblyAuger and Extruding Head Removal Overload Check Safety ControlsElectrical Checkout Compressor CheckCustomer Comments Troubleshooting Troubleshooting Chart Icemaker not Operating2006, IMI Cornelius Inc Publication Number 630460324SER IMI Cornelius Inc

WCF1411-A specifications

The Cornelius WCF1411-A is a high-performance beverage dispensing system designed to meet the demands of both commercial and light industrial applications. This innovative unit serves as an ideal solution for businesses looking to provide a variety of cold beverages efficiently and effectively.

One of the standout features of the WCF1411-A is its capacity to dispense multiple beverages from a single unit. With the ability to host numerous flavor options, this system caters to diverse consumer preferences. Operators can select from a range of beverages, including soft drinks, flavored waters, and even iced coffees, making it a versatile addition to any beverage service setup. This capability not only enhances customer satisfaction but also streamlines inventory management.

The WCF1411-A utilizes advanced cooling technology, ensuring that drinks are consistently chilled to the perfect serving temperature. This is achieved through its efficient refrigeration system, which minimizes energy consumption while maintaining optimal performance. The dual-cooled setup provides precise temperature control, ensuring that each beverage is served refreshing, enhancing the overall quality and flavor.

Moreover, the Cornelius WCF1411-A is designed with user-friendly features. The intuitive interface simplifies the dispensing process, allowing staff to quickly serve beverages with minimal training. Additionally, the unit is equipped with a durable stainless steel construction, which not only increases its longevity but also makes it easy to clean and maintain. This durability is particularly useful in high-traffic environments, where the system is subjected to regular use.

Another notable characteristic of the WCF1411-A is its compact design. This makes it suitable for spaces with limited room, such as small restaurants, cafes, and convenience stores. Despite its smaller footprint, the system does not compromise on performance, delivering similar capabilities to larger units.

Furthermore, the WCF1411-A is compatible with various beverage mixers, allowing operators to expand their offerings with ease. Its flexible connectivity options enable integration with existing systems, providing seamless operation within various environments.

In conclusion, the Cornelius WCF1411-A stands out as a reliable and efficient beverage dispensing solution. With its multi-beverage capability, advanced cooling technology, user-friendly features, durable construction, and compact design, it addresses the needs of modern beverage service operators, ensuring delightful drink experiences for customers while maximizing operational efficiency.