Foster FMIC180 manual Alarm Conditions, PC Board Set Up

Page 8

block releasing it from the mould. Once released the ice block drops into the storage bin below and breaks into individual cubes, in the process it moves the deflector plate forwards. The defector has on its side a magnetic switch that when it moves forward it opens and closes the contacts. This motion deactivates the relay contacts that control the hot gas and water drain valve allowing the unit to start a new freezing cycle.

When the ice bin is full of ice, the last batch of ice released from the evaporator cannot continue into the bin and so it stops the deflector from returning to its position. With the magnetic switch contacts remaining open for more than 30 seconds the entire unit stops with the glowing of the Amber bin full LED.

The machine will restart when the deflector returns to its normal position provided the machine has been of for more than 3 minutes, if not the start will be delayed for 3 minutes with the blinking of the green Machine In Operation LED.

5.Alarm Conditions

Power On.‘Green’.

Bin Full/ Washing. ‘Amber’. High Pressure. ‘Red’.

 

 

 

 

 

 

Machine in Operation ‘Green’.

Alarm ‘Red’.

Reset / Washing. ‘Push Button’.

The two Red LED’s are glowing constantly.

Condenser Sensor faulty.

The two Red LED’s are blinking slowly.

Water Error. The water level inside the reservoir is to low after 3 minutes from start of the water inlet valve being activated.

The two Red LED’s are blinking fast.

Reset Mode. Charging water through the Water Solenoid Valve after tripping OFF on Water Error.

The Red Alarm LED is glowing continuously.

Harvest cycle longer than 3 minutes 30 seconds.

The Red Alarm LED is blinking slowly.

Too High Condensing Temperature: The Condenser Sensor detected a temperature above 65° C.

The Red Alarm LED is blinking fast.

Reset Mode: Condenser Sensor sensing condenser temperature below 50° C, fan motor in operation for 3 minutes then back on to Start Up Cycle Mode.

Red High Pressure LED is glowing continuously.

Too High Discharge Pressure, exceeding 33 bar (460 PSI).

Red High Pressure LED is blinking fast.

RESET MODE: After pushing the Red Reset Button of the Pressure Control (located at the rear of the machine) firstly the fan motor runs for 3 minutes then back on to the Start Up Cycle Mode.

The PC Board also checks the maximum time of the freeze cycle that may change according to the operation of the fan motor during the freezing cycle (relative to room temperature).

Fan motor in ON/OFF Mode: Maximum Freeze Cycle length equal to 30 minutes.

Fan motor ON All of the time: Maximum Freeze Cycle length equal to 40 minutes.

Whenever the machine remains in the Freezing Cycle for the Maximum time ( 30 or 40 minutes) the PC Board moves the unit directly into the Harvest Cycle.

6.PC Board Set Up

The PC Board can be set up for Manual Reset Mode with the Jumper In Place.

Manual Reset Mode. (Jumper in place)

To Restart the Machine it is necessary to Push the Reset Button.

The PC Board can be set up for Automatic Reset Mode with the Jumper Out Of Place.

Automatic Reset Mode. (Jumper out of place)

The Automatic Reset Mode is activated only for the following ALARM CONDITIONS.

WATER ERROR

TOO HIGH CONDENSING TEMPERATURE

TOO LONG HARVEST CYCLE.

6.1Water Error

The machine remains in OFF mode for 30 minutes then it tries to re-fill with water.

Fills with water: Machine remains in operation.

Fails to fill with water: Machine again in the OFF mode for a further 30 minutes.

6.2Too High Condensing Temperature

As soon as the temperature registered by the Condenser Sensor is above 50° C, the PC Board starts up firstly the condenser fan motor for 3 minutes then the entire machine through the normal Start UP Cycle Mode.

After the 3 minutes 30 seconds of the Harvest Cycle, the PC Board moves the machine into a new Freezing Cycle.

CAUTION: If the factory seal is broken on the replacement drier, exposing it to the atmosphere for more than a few minutes, the drier will absorb moisture from the atmosphere and lose substantial ability for moisture removal.

To replace the drier:

1.Remove the factory seals from the replacement drier and install the drier in the refrigerant lines with the arrow positioned in the direction of the refrigerant flow.

2.Solder the drier into the lines, two places, taking precautions NOT TO OVERHEAT the drier body, during installation soldering.

3.Purge the system and check for leaks.

4.Thoroughly evacuate the system to remove moisture and non- condensables.

5.Charge the system with refrigerant, by weight. SEE NAMEPLATE.

6.Replace and attach front and left side panel.

9.10Removal and Replacement of the Evaporator Plate Assembly

1.Remove front and top panels.

2.Store refrigerant charge in liquid receiver and isolate parts to be opened from the rest of the system.

3.Disconnect water distributor tube above the evaporator plate and remove it.

4.Unsnap and remove evaporator cover deflector.

5.Loosen and remove all screws securing the evaporator frame to the chassis.

6.Unsolder and remove the refrigerant lines at the top of the evaporator plate to be replaced.

7.Remove nuts at top and left and right side of the evaporator to remove top and side trimming that make-up the frame of the evaporator

plate. The evaporator plate is now free.

To replace the evaporator plate, reverse the removal procedures. See nameplate. Weight in proper charge of R22/R404A.

9.11Water Regulating Valve - Water Cooled

1.Shut off water.

2.Remove front and right side panel.

3.Unscrew water inlet fitting connection at the water regulator valve to condenser bracket.

4.Purge system of refrigerant.

5.Unscrew fitting connection at outlet of valve.

6.Unsweat valve connection from ‘T’ joint on system liquid line.

7.Remove valve from machine.

Reverse to reassemble.

9.12Thermostatic Expansion Valve

1.Remove front, top and right side panels.

2.Purge system of refrigerant.

3.Unsweat valve at inlet, equaliser, and outlet.

4.Remove insulation from valve bulb, remove mounting straps and valve from cabinet.

5.Place new valve bulb in same place as old valve, secure with straps, and reinsulate. Reverse to reassemble.

NOTE: Always install a replacement drier, any time the sealed refrigeration system is opened. Do not replace the drier until all other repair or replacement has been completed.

Thoroughly evacuate the system to remove moisture and non-condensables.

9.13Fan Motor or Blade - Left and Right Side

1.Remove left or right side service panels.

2.Remove screws and fan motor shroud.

3.Unplug fan motor to be removed.

4.Remove fan motor bracket from upper tie rod of unit chassis.

5.Remove fan blade from motor. Note location on motor shaft, and hub position.

6.To also replace fan motor, remove it from bracket.

Reverse to reassemble.

NOTE: When replacing a refrigeration component, the exact refrigerant charge must be WEIGHED or metered into a completely evacuated system, because the FMIC is a CRITICALLY charged system.

8

21

Image 8
Contents N u a l F200 & F300 Modular Ice Cuber Fmic 180 & 260 Electronic Modular Ice Cuber Capacities F200 F300 SpecificationGuidelines for Icemaker Bin Lids Installation Instructions Keep OUT of the Reach of ChildrenService Diagnosis Maintenance and Cleaning InstructionsStart Up Harvest CycleWiring Diagrams 180+260WiringDiagram AirCooled220V.50Hz1ph180+260WiringDiagram WaterCooled220V.50Hz1ph OperationAlarm Conditions PC Board Set UpRemoval and Replacement Procedures Component DescriptionWiring Diagram F200 & F300 Electronic Control Board Service SpecificationToggle Switch ICE/OFF/WASH Water System Maintenance, Cleaning and Sanitation InstructionsIcemaker Fmic 180 Machine Specifications R22 Machines Fmic 180 Machine Specification R404A MachinesFmic 260 Machine Specifications R22 Machines Fmic 260 Machine SpecificationFor The Installer For The PlumberFor The Electrician Start-Up

FMIC180 specifications

The Foster FMIC180 is a cutting-edge industrial fan designed for optimal airflow and efficient cooling in various environments. This powerful fan is ideal for use in production facilities, workshops, and large commercial spaces, where maintaining a stable temperature is crucial for both equipment and personnel comfort. With its impressive features and robust design, the FMIC180 stands out in the competitive market of industrial fans.

One of the standout characteristics of the FMIC180 is its high-performance motor, which delivers substantial airflow while ensuring energy efficiency. The motor is built with durable materials, providing longevity and reliable operation even in demanding conditions. Additionally, the FMIC180 is equipped with a variable speed control system, allowing users to adjust the airflow according to their specific needs. This versatility makes it suitable for a variety of applications, from gentle air circulation to powerful cooling.

The design of the FMIC180 emphasizes user-friendliness and ease of maintenance. Its lightweight structure allows for effortless relocation within the workspace, while integrated handles enhance maneuverability. The fan’s easy-access components simplify routine maintenance tasks, ensuring that it remains in peak operating condition with minimal effort.

An essential feature of the Foster FMIC180 is its robust build quality. Constructed with high-grade materials, the fan is designed to withstand the rigors of industrial environments. Its protective housing guards against dust and debris, ensuring reliable performance even in challenging conditions. The fan’s blades are aerodynamically designed to maximize airflow efficiency, reducing the energy consumption typically associated with high-volume fans.

In terms of safety, the FMIC180 includes built-in thermal protection that prevents overheating and potential damage to the motor during extended use. Its stable base design minimizes vibrations, providing a secure operation without the risk of tipping over.

The Foster FMIC180 prioritizes compatibility and integration within existing industrial setups. Its standard power requirements allow for seamless connection to existing electrical systems, making installation straightforward. With these advanced features and technologies, the Foster FMIC180 emerges as an essential component in industrial cooling solutions, promoting enhanced airflow and operational efficiency across various applications. Its combination of performance, durability, and user-centric design makes it a reliable choice for businesses looking to improve their environmental conditions while ensuring energy efficiency.