Dometic RGE400 manual Operating Instructions, Testing LP GAS Safety Shutoff, Electrical Connection

Page 3

DO NOT use a flame to check for gas leaks.

The gas supply system must incorporate a pressure regulator to maintain a supply pressure of not more than 11 inches water column.

When testing the gas supply system at test pressures in excess of l/2 psig, the refrigerator and its individual shutoff valve must be disconnected from the gas supply piping system.

When testing the gas supply system at pressures less than or equal to 1/2 psig, the appliance must be isolated from the gas supply piping system by closing its individu- al manual shutoff valve.

In case detailed instructions on the installation and connection to the gas supply are required, contact your dealer or distributor.

TESTING LP GAS SAFETY

SHUTOFF

The gas safety shut-off must be tested after the refrigerator is connected to the LP gas supply.

To test the gas safety shut-off, proceed as follows:

1.Start the refrigerator according to the instructions for Gas Operation, section “Operation Instructions”.

2.Check that the gas flame is lit. This can be observed through the reflector (E).

3.Close the gas valve by turning the knob (A) back to “OFF” position.

4.Wait for one minute.

5.Remove burner cover plate, one screw at the burner. Open the gas valve by turning the knob (A) to position “GAS” without pushing the buttons (C)and(D). Apply a non-corrosive commercial bubble solution to the burner jet.

6.No bubbles should appear at the opening of the burner jet. The presence of bubbles indicates a de- fective gas safety shutoff, and service is required.

7.If no bubbles were present at the burner jet, the gas safety valve is working properly. Rinse jet thoroughly with fresh water before proceeding. Be careful not to damage the burner jet. Replace burner cover plate and turn the knob (A) back to “OFF’. Start the refrig- erator by following the instructions for Gas Operation, section “Operation Instructions”. Normal operation of the burner should return. Allow the burner to operate for a minimum of 5 minutes.

ELECTRICAL CONNECTION

120 Volt AC Connection

The refrigerator is equipped with a three-prong (ground- ing) plug for your protection against shock hazards and should be plugged directly into a properly grounded three-prong receptacle. DO NOT cut or remove the grounding prong from this plug. The cord should be routed to avoid direct contact with the burner cover, flue cover or any other components that could damage the cord insulation.

OPERATING INSTRUCTIONS

IMPORTANCE OF LEVELING A REFRIGERATOR

In an absorption refrigerator system, ammonia is lique- fied in the finned condenser coil at the top rear of the refrigerator. The liquid ammonia then flows into the evaporator (inside the freezer section) and is exposed to a circulating flow of hydrogen gas, which causes the ammonia to evaporate, creating a cold condition in the freezer.

When starting this refrigerator for the very first time, the cooling cycle may require up to four hours of running time before the cooling unit is fully operational.

The tubing in the evaporator section is specifically sloped to provide a continuous movement of liquid am- monia, flowing downward by gravity through this section. If the refrigerator is operated when it is not level, liquid ammonia will accumulate in sections of the evaporator tubing. This will slow the circulation of hydrogen and ammonia gas, or in severe cases, completely block it, resulting in a loss of cooling.

The refrigerator must be adjusted to a vertical position in both directions.

Use the feet on the refrigerator to adjust its position.

CONTROLS

FIG.3.

The refrigerator can be run on either 120 volt AC or LP gas. Changing between these modes of operation is carried out by means of control buttons positioned as shown in fig. 3.

The energy selector (A) can be set at either “ELEC”(120 volt AC), “GAS” (LP gas) or “OFF”.

The refrigerator temperature is controlled by a thermo- stat (6). Please note that the thermostat has no “off” position.

The refrigerator is fitted with a safety device which automatically shuts off the supply of gas if the flame goes out. The safety device can be opened manually by depressing knob (C).

The piezoelectric igniter discharges sparks over the burner when the button (D) is pushed.

In the flame viewer (E) you can see a blue light when the flame is alight.

Image 3
Contents Avis Installation and Operating InstructionsFor Your Safety Refrigerator for LP-GAS and Electric OperationClearances InstallationFREE-STANDING Model for Floor Installation only General InstructionControls Testing LP GAS Safety ShutoffOperating Instructions Electrical ConnectionThermostat HOW to USE the Refrigerator Food Storage CompartmentGAS Operation Electric OperationMaintenance & Service CleaningShut OFF Storage Procedure Electrode To 3/16 Burner tube Spare Parts TroubleshootingRefrigerator Dimensions Refrigerator Does Not Cool Properly