York PC9*DH warranty AIR Flow Data, Jumper Settings

Page 3

246815-YTG-D-0108

AIR FLOW DATA

HIGH / LOW SPEED COOLING AND HEAT PUMP CFM

PC9B12N060DH11

PC9B12N080DH11

JUMPER SETTINGS

 

CFM

 

CFM

 

 

 

 

High

 

Low

High

 

Low

COOL Tap

ADJ Tap

1330

 

900

1310

 

890

A

B

1130

 

800

1100

 

740

B

B

1220

 

850

1220

 

830

A

A

1040

 

730

1000

 

670

B

A

1120

 

770

1090

 

720

A

C

920

 

650

900

 

610

C

B

950

 

660

880

 

610

B

C

740

 

540

680

 

510

D

B

860

 

610

810

 

580

C

A

690

 

540

630

 

500

D

A

790

 

570

730

 

530

C

C

630

 

530

590

 

500

D

C

PC9C16N080DH11

PC9C20N100DH11

 

 

PC9C16N100DH11

JUMPER SETTINGS

 

 

 

 

CFM

 

CFM

 

 

High

 

Low

High

 

Low

COOL Tap

ADJ Tap

1660

 

1110

2210

 

1480

A

B

1550

 

1050

1780

 

1180

B

B

1610

 

1070

2040

 

1350

A

A

1440

 

960

1620

 

1050

B

A

1470

 

990

1840

 

1250

A

C

1370

 

920

1560

 

1010

C

B

1290

 

850

1470

 

940

B

C

1130

 

790

1370

 

890

D

B

1230

 

850

1460

 

930

C

A

1050

 

720

1250

 

790

D

A

1110

 

760

1310

 

810

C

C

950

 

660

1090

 

690

D

C

PC9D20N120DH11

 

 

 

JUMPER SETTINGS

 

CFM

 

 

 

 

 

 

 

 

 

High

 

Low

 

 

 

COOL Tap

ADJ Tap

2280

 

1510

 

 

 

A

B

1860

 

1190

 

 

 

B

B

2090

 

1370

 

 

 

A

A

1630

 

1060

 

 

 

B

A

1880

 

1250

 

 

 

A

C

1620

 

1030

 

 

 

C

B

1500

 

960

 

 

 

B

C

1410

 

880

 

 

 

D

B

1490

 

920

 

 

 

C

A

1290

 

790

 

 

 

D

A

1360

 

840

 

 

 

C

C

1140

 

690

 

 

 

D

C

All CFM’s are shown at 0.5” w.c. external static pressure.These units have variable speed motors that automatically adjust to provide constant CFM from 0.0” to 0.6” w.c. static pressure. From 0.6” to 1.0” static pressure, CFM is reduced by 2% per 0.1” increase in static. Operation on duct systems with greater than 1.0” w.c. external static pressure is not recommended.

NOTE: At some settings, LOW COOL airflow may be lower that what is required to operate an airflow switch on certain models of electronic air cleaners. Consult the instructions for the electronic air cleaner for further details.

NOTES:

1. Airflow expressed in standard cubic feet per minute (CFM).

Unitary Products Group

3

Image 3
Contents Natural GAS WarrantyFeatures DescriptionMBH CFM Electrical and Performance DataAIR Flow Data Jumper SettingsFilter Performance Pressure Drop Inches W.C. and KPA Filter PerformanceApplying Filter Pressure Drop to Determine System Airflow Filter SizesVariable Speed Modulating Furnace TWO Stage AIR Conditioner AC 26AThermostat ID ModelsVariable Speed TWO Stage Modulating AIR Furnace Conditioner AC 26BDHM AC 26CVariable Speed Modulating Furnace TWO Stage AIR ConditionerTWO Stage Heat Pump OD ModelsVariable Speed Modulating PP32U70124 DN22H00124 DP22U70124Accessories YTG-D-0108 Unitary Products Group Unitary 5005 Norman Products York Group Drive 73069