(i)A separate shut-off valve for each oven must be provided. It should be as close as possible to the place where the gas supply line goes into the oven. It must be located such that it is easily accessible.

(j)When stacking with another oven, two shut-off valves, one for each of the two ovens, must be provided.

After the Gas Supply has been connected, it is extremely important to check all the piping for leaks. Use a soap and water solution or a product expressly made for this purpose. Do not use Matches, Candles or a flame etc to check leaks since these methods are extremely dangerous.

6. FLUE CONNECTION - VENTILATION:

(a) INSTALLATION UNDER VENTILATION HOOD (STANDARD):

If the oven is installed under a collection hood, use the flue diverter (fig.1) supplied. Local inspectors and ventilation and environmental specialists should be consulted so that the design and the installation of the hood conforms to the local / municipal codes (see fig.3).

(b)DIRECT VENTING (Optional) – NOT AVAILABLE FOR EUROPEAN COMMUNITY COUNTRIES: If direct venting, it is necessary to install a draft hood (fig.2). The flue pipe from the draft hood must not run downwards at any point from the oven to the final outlet. It should always slant slightly upwards. For best results it should rise straight up.

NOTE: Do not put a damper in the flue and do not connect a blower directly to the flue. If the flue runs directly to the free air outside the building, use a wind deflector or a UL listed vent cap at the end of the flue pipe. Termination of the vent must be at least 2 feet above the highest part of the roof within 10 feet (Ref: American Gas Association Catalog No. XH0474).

Figure #1

Flue Diverter

(For use w/Collection Hood)

Figure #2

Figure #3

BAKERS PRIDE

Draft Hood

(For use w/Direct Venting)

7. MAIN BURNER SAFETY PILOT OPERATION:

The purpose of the safety pilot system is to lock the gas supply to the main burner at the combination valve, if for any reason the pilot burner is not lit. Oven should be relighted by following the steps given below. However, in normal service, the pilot flame stays lit indefinitely, day and night or weekends. This prolongs the life of the safety valve.

The safety pilot valve is in effect a two-stage control. After initial lighting, the pilot burner stays on without the gas cock dial being held pressed in. After 1-2 minutes, the valve opens fully to let the gas flow past the safety pilot valve into the burner system.

7

Image 7
Contents Bakers Pride Oven CO., INC Installation and Operating InstructionsFor Your Safety Important InstructionsIII. Cleaning and Maintenance Installation InstructionsII. Operating Instructions Model Models CoveredReceiving Clearances SET UP The oven must be installed in a well-ventilated areaMounting Legs Pizza Deck Installation with Casters OptionalTwo Deck Installation Three Deck InstallationGAS and Electric Connections Four Deck InstallationMain Burner Safety Pilot Operation Installation Under Ventilation Hood StandardFlue Connection Ventilation Thermostat Calibration Pilot Burner Lighting ProcedurePilot Burner Flame Adjustment Burner OperationBreaking Lighting ProcedureRecommended Operating Procedure Flame Diverters1B. Painted Surfaces BakingHelpful Hints 1A. Oven ExteriorBurner Compartment Flue VentOven Interior Baking ChamberBakers Pride Oven CO., INC