Lifebreath CAF-02-MB installation manual Plumbing, Water Heater

Page 28

Plumbing

In order to improve serviceability of our products, the check valve is included with our manual kit for field installation between the air-handler and hot water source.

The check valve should be installed in a vertical run of pipe with the flow of water in an upward direction.

An arrow on the check valve indicates its correct orientation and must match the direction of water flow.

This will allow for ease of service to remove any installation debris or service required due to extended hard water conditions.

Note: Take care during soldering to avoid debris or solder from lodging in the check valve.

Note: It is critical to follow the piping configuration shown. Maintain a minimum distance of 12” above the CAF/AH. This will minimize thermal siphoning in the combo system.

Figure 1

To

 

House

 

Water

Heater

Check

Valve

Min. 12" above 12" top of CAF / AH

CAF

or

AH

Figure 2

To

House

Water

Heater

Check

Valve

Min. 12" above 12" top of CAF / AH

CAF

or

AH

*It should be noted that problems have been observed when using the side tappings on certain water heaters; therefore, it is strongly recommended to use the top water tappings as indicated in Figure 1 to minimize thermal siphoning and related issues.

For further information, please contact Technical Support (519) 457-1904.

28

Image 28
Contents OPERATION, Sizing and Installation Manual Table of Contents Introduction HRV Aluminum CoreDescription and Purpose Important NoteCombo System Basic Principles Closed/Open Combo SystemCall for Space Heating Only Operation Call for Domestic Hot Water and Space Heating OperationAir System Water PipingManual Valves Shut Off Valves Drain ValveThrottling Valve Check ValvesOff Season Circulation Timer Expansion TanksCold WaterAir Handler Return Air Temperature Air Handler Temperature RiseWater Heater Thermostat Room ThermostatDesign vs. Field Conditions Water System PressuresHead Pressure Flow RateModel Number Nomenclature Breakdown Specifications Model CAF-U-S4A-24-P16 Dimensions & ClearancesWarranty Core Filters CaseSpecifications Model CAF-U-L4A-36-P16 CAF-U-L4A-36-P16Filters Case Specifications Model CAF-D-S4A-24-P16CAF-D-S4A-24-P16 Specifications Model CAF-D-L4A-36-P16 CAF-D-L4A-36-P16CAF-H-S4A-24-P16 Specifications Model CAF-H-S4A-24-P160302 Specifications Model CAF-H-L4A-36-P16 CAF-H-L4A-36-P16Specifications Model CAF-U-L2A-48-P16 CAF-U-L2A-48-P16CAF-U-00-36-P16 Specifications Model CAF-U-00-36-P160211 CAF-U-00-48-P16 Specifications Model CAF-U-00-48-P160209 Installation Locating The UnitDuct Connections Option 1 Ventilation Ports Off Left SideOption 2 Ventilation Ports Off Right Side DuctingLocating Intake Weatherhood Locating the Exhaust WeatherhoodsOutside Ducting the Weatherhoods Locating WeatherhoodPitot Tube Air Flow Balancing Balancing ProcedurePrior to balancing, ensure that Pitot Tube and Gauge Placement of the Pitot TubeBalancing Collar Instructions Drain Line HRV Drain Line DiagramPiping Plumbing Water HeaterBasic Functions Automatic Self TestSelecting Different Heat & Cool Speeds ECM Motor Settings Off Season Circulation Timer OperationHeating/Cooling VentilationStart-Up Procedure Following conditions must be met prior to start-upTroubleshooting Humidity levels are too low Humidity levels are too highWater Pump Performance Specifications System CommissioningPage Page Page Page Page Page Diagram ECM CAF/Air Handler Wiring Diagram Fan Motor