Troubleshooting

Lack of heat

1.Check that the room thermostat is set to the desired temperature.

2.Confirm the units have power and the shut-off valves are open.

3.Ensure there is power to the unit and that the pump is working. If the pump is not working properly it may be stuck. Disconnect power and remove screw in center face of the pump. Using a screwdriver, turn the pump shaft sev- eral times to free it from sticking. Replace center-screw and re-connect power. If pump still fails to start, it may require replacement.

4.Confirm that the hot water heater is working and that hot water is entering the Clean Air Furnace.

5.Verify that the airflow in and out of the system matches designed specs. If airflow is low, check for blockage in the filter or some other obstruction.

6.Make sure your water heater is sized large enough for heat load of house and for domes- tic hot water use.

7.Air may still be in the water lines. If so, re- purge the system according to the start up procedure.

8.Confirm that the inlet and outlet pipe connec- tions are not reversed.

9.Ensure that there are no other restrictions in the water lines, such as faulty valves, or debris.

Pump is noisy

Pumps can become noisy when air remaining in the lines interfere with their operation. If this occurs re-purge the system as indicated in the Start-Up Procedure.

HRV core freezes up

1.Make sure that the supply and exhaust lines are balanced according to the "Balancing Procedure" in this manual.

2.If out of balance, ensure that the balancing dampers have not been moved and that there are no obstructions in the outside hoods.

During cooling cycle, hot water circulates through the coil

If the check valve inside the cabinet is stuck in the open position, hot water may infiltrate the heating coil. This occurs when the hot pipes are not capped-off during installation or service and for- eign debris enters the piping. This debris can set- tle under the check valve seat and permit hot water to flow into the coil. The problem can be cor- rected by repeatedly flushing the heating loop until it is clean.

Water sits in drain pipes

1.Check drain pans or lines for plugs.

2.Confirm that the HRV core is installed according to manufactures recommendations.

3.Check the drain line for kinks.

4.Make sure that the O-ring in the drain nozzles sit flat.

5.Ensure the drain line has enough "fall" to it.

Condensation/ice forming inside ventilation ducts

A rip in the vapor barrier or poorly sealed joints may cause condensation or ice to form on the ducting. If this occurs, replace the entire line.

33

Image 33
Contents OPERATION, Sizing and Installation Manual Table of Contents HRV Aluminum Core IntroductionImportant Note Description and PurposeClosed/Open Combo System Combo System Basic PrinciplesCall for Domestic Hot Water and Space Heating Operation Call for Space Heating Only OperationAir System Water PipingManual Valves Drain Valve Shut Off ValvesThrottling Valve Check ValvesExpansion Tanks Off Season Circulation TimerCold WaterAir Handler Temperature Rise Air Handler Return Air TemperatureWater Heater Thermostat Room ThermostatWater System Pressures Design vs. Field ConditionsHead Pressure Flow RateModel Number Nomenclature Breakdown Dimensions & Clearances Specifications Model CAF-U-S4A-24-P16Warranty Core Filters CaseCAF-U-L4A-36-P16 Specifications Model CAF-U-L4A-36-P16Specifications Model CAF-D-S4A-24-P16 Filters CaseCAF-D-S4A-24-P16 CAF-D-L4A-36-P16 Specifications Model CAF-D-L4A-36-P16Specifications Model CAF-H-S4A-24-P16 CAF-H-S4A-24-P160302 CAF-H-L4A-36-P16 Specifications Model CAF-H-L4A-36-P16CAF-U-L2A-48-P16 Specifications Model CAF-U-L2A-48-P16Specifications Model CAF-U-00-36-P16 CAF-U-00-36-P160211 Specifications Model CAF-U-00-48-P16 CAF-U-00-48-P160209 Locating The Unit InstallationDuct Connections Option 1 Ventilation Ports Off Left SideDucting Option 2 Ventilation Ports Off Right SideLocating the Exhaust Weatherhoods Locating Intake WeatherhoodOutside Ducting the Weatherhoods Locating WeatherhoodBalancing Procedure Pitot Tube Air Flow BalancingPrior to balancing, ensure that Placement of the Pitot Tube Pitot Tube and GaugeBalancing Collar Instructions HRV Drain Line Diagram Drain LinePiping Water Heater PlumbingAutomatic Self Test Basic FunctionsSelecting Different Heat & Cool Speeds ECM Motor Settings Operation Off Season Circulation TimerHeating/Cooling VentilationFollowing conditions must be met prior to start-up Start-Up ProcedureTroubleshooting Humidity levels are too high Humidity levels are too lowSystem Commissioning Water Pump Performance SpecificationsPage Page Page Page Page Page Diagram Fan Motor ECM CAF/Air Handler Wiring Diagram