Field Controls PVU-300 Vent Pipe Fittings Vent Pipe Diameter TEE Elbow Reducer

Page 3

PROCEDURE FOR CALCULATING TOTAL EQUIVALENT PIPE LENGTH IN FEET

1.Calculate the total equivalent feet for each type of fitting used in the venting system from the following chart.

2.Calculate the total amount of feet for the straight lengths of vent pipe.

3.Add the equivalent feet for the fittings with the total amount of feet of straight lengths.

Table 3

EQUIVALENT LENGTH (FEET) OF VENT PIPE FOR VENT PIPE FITTINGS

 

VENT PIPE FITTINGS

 

 

 

 

 

 

 

 

VENT PIPE DIAMETER

 

 

 

 

 

 

 

 

 

 

 

3”

 

 

4”

 

 

5”

 

 

6”

 

 

7”

 

 

8”

 

 

9”

 

 

10”

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TEE

 

 

 

19

 

25

 

31

 

38

 

44

 

 

50

 

56

 

63

 

 

90° ELBOW

 

 

 

5

 

7

 

9

 

11

 

12

 

 

14

 

16

 

18

 

 

45° ELBOW

 

 

 

3

 

4

 

4

 

5

 

6

 

 

7

 

8

 

9

 

 

REDUCER

 

 

1/4

 

 

8

 

11

 

14

 

17

 

19

 

 

22

 

25

 

28

 

 

 

 

1/2

 

 

5

 

7

 

8

 

10

 

12

 

 

13

 

15

 

17

 

 

(d/D)*

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3/4

 

 

2

 

3

 

3

 

4

 

4

 

 

5

 

6

 

6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*Reducer or increaser ratio (d/D) small diameter divided by the larger diameter. (See Figure 3)

Example: 4" to 8" reducer, the reducer ratio is d/D = 4/8 = 1/2. To estimate the equivalent foot length for the fitting, use the smaller pipe diameter for the equivalent length figure. Example: 4" to 8" reducer; the reducer ratio is 1/2 and the smaller pipe

diameter is 4". So, from the chart, the equivalent feet would be 7 feet.

Example: System Pipe Size = 4"

Step 1 2 – 90° Elbows (4") = 14 Ft.

Step 2 10 - 2 Ft. Lengths of 4" Pipe = 20 Ft.Figure 3

Step 3 Total Equivalent Feet = 14 Ft. + 20 Ft. = 34 Ft.

INSTALLATION SAFETY INSTRUCTIONS

CAUTION: This device must be installed by a qualified installer in accordance with the manufacturer's installation instructions. Appliances should have a minimum of 75% combustion efficiency or have a maximum measured flue gas temperature of 550°F at the inlet of the venter.

1.The power venting system must be installed by a qualified installer. "Qualified Installer" shall mean an individual who has been properly trained or a licensed installer. The installer must write or imprint his name, phone number and date of installation on the installation tag. The tag should be attached to the power venter unit. Recording burner and venting system initial operational information is recommended as a guide for service or burner tune-up. Enter this on the back page of this manual.

2.Safety inspection of a venting system should be performed before and after installing a power venting system on an existing or new appliance. Procedures to follow are those recommended by the National Fuel Gas Code, A.N.S.I.Z223.1 or refer to the "General Installation Inspection" section of this manual.

3.Plan the vent system layout before installation to avoid the possibility of accidental contact with concealed wiring or plumbing inside walls.

4.Single wall vent pipe may be used to join an appliance to the venting system, but if proper clearances cannot be maintained from combustible materials, Class B Vent Pipe should be used for gas appliances. Refer to national or local codes for guidelines. Also, a minimum of 6 inches clearance between the venter housing and combustible materials must be maintained.

5.Disconnect power supply before making wiring connections to prevent electrical shock and equipment damage.

6.This equipment is designed to overcome minor negative pressure conditions. To ensure extreme negative pressure does not exist, follow the "General Installation Inspection" section of this manual.

7.Heating appliances equipped with draft hoods, such as boilers or furnaces, LP and natural gas appliances SHOULD have a secondary spillage switch installed. On appliances without draft hoods, it is recommended that the secondary safety switch GSK-3 be installed into the system. Gas-fired 30 millivolt power systems MUST be equipped with a spillage switch.

Page 3

Image 3
Contents Do not Destroy These Instructions Must Remain with Equipment Typical Venting System ComponentsSystem Operation Power Venter SizingVent Pipe Fittings Vent Pipe Diameter TEE Elbow Reducer Installation Safety InstructionsInstallation of Power Venter Side Wall Vent Hood Installation Diagram B Internal Wiring Schematic for PVU-300 General Wiring Instructions Adjusting Thermostat Anticipator General Installation Inspection AIR Flow AdjustmentsReplacement Parts List System Control Check ProceduresTroubleshooting Tips MaintenanceMultiple Venting Systems Diagram G Multiple Wiring with two 24 VAC Appliances Diagram H Multiple Wiring with two 120 VAC Appliances PV Series Power Venter Vertical Venting Option Venting System Operational Information Installation Information46517200 Rev B 11/06

PVU-300 specifications

Field Controls PVU-300 is a highly esteemed device in the realm of indoor air quality management, particularly designed for residential and light commercial applications. This innovative product excels in providing a comprehensive solution for ventilating spaces while ensuring optimal comfort and air quality.

One of the main features of the PVU-300 is its capability to deliver fresh outdoor air efficiently into a building while exhausting stale indoor air. This is crucial for maintaining a healthy living or working environment. The unit comes equipped with multiple airflow configurations, allowing it to adapt seamlessly to various building sizes and layouts.

The PVU-300 utilizes advanced demand control ventilation technology, which adjusts ventilation rates based on the actual occupancy and indoor air quality needs. This not only enhances comfort but also improves energy efficiency, as the system reduces unnecessary energy consumption during periods of low occupancy.

Furthermore, the PVU-300 is designed with intuitive controls that allow for easy operation and monitoring. The user-friendly interface simplifies adjustments and settings, ensuring that users can easily manage their ventilation needs. This device is compatible with a range of sensors, enabling it to work in conjunction with CO2 and humidity controls, further optimizing performance.

In terms of construction, the PVU-300 is built with durability in mind. Its robust design ensures longevity and reliable operation in various environmental conditions. The unit also boasts a compact footprint, making it suitable for installation in tight spaces without compromising airflow performance.

The technology behind the PVU-300 includes high-efficiency fans that minimize noise levels while maximizing airflow. This ensures that the device operates quietly, providing a comfortable environment without distracting sounds.

Installation of the PVU-300 is straightforward, thanks to its flexible duct design and user-friendly mounting options. This efficiency not only saves time but also reduces labor costs associated with installation.

In conclusion, the Field Controls PVU-300 represents a significant advancement in ventilation technology, combining energy efficiency, user-friendliness, and adaptability to diverse environments. Its features and technological innovations make it an ideal choice for enhancing indoor air quality, ensuring spaces are both comfortable and healthy for occupants.