Beckett SL6150, SLD375, SL5125, SLD4100, SLD5125, SL375 Burner Installation, Direct Vent OIL Burners

Page 15

15

DIRECT VENT OIL BURNERS

Riello Burners

All Riello direct vent burners are shipped with the nozzle for the SLD375 installed. A separate nozzle is included in the burner carton for the SLD4100 and SLD5125. See the burner set up page or the Installer Serviceman Label attached to the boiler. for the appropriate burner settings.

Boilers supplied with Riello burners will also be supplied with a 3” to 4” galvanized adapter.

The adapter is to be fastened directly to the flange opening on the burner cover using three sheet metal screws.

The Riello BF5 burners for use with direct vent systems are shipped with the controls, which provide pre and post purge. Pre purge is provided to ensure clean starts under all conditions. Post purge is provided to ensure that the boiler fires at maximum efficiency and dependability throughout the heating season. Post purge timing is variable. The factory set post purge timing should be set at approximately 45 seconds. Post purge times in excess of 60 seconds when using the Riello burner will cause the Honeywell Aquastat to lock out on an error code Err4 B1 fault.

Beckett Burners

Boilers supplied with the Beckett NX burner are supplied with an inlet air adapter which must be installed in place of the inlet air louvers. Refer to the Beckett NX burner manual.

Beckett NX burners for use with direct vent systems are shipped with the controls, which provide pre and post purge. Pre purge is provided to ensure clean starts under all conditions. Post purge is provided to ensure that the boiler fires at maximum efficiency and dependability throughout the heating season.

Post purge of the oil burner is controlled through the electronic circuitry supplied on the oil burner primary control. The factory set post purge timing is set at approximately one minute.

Burner Installation

The burner is mounted to the door with (4) 8mm studs, nuts and washers (located in the burner trim bag). Thread the (4) studs in to the (4) M8 holes threaded to permit connection to the burner. Thread the shorter length of stud into cast door.

Check that the correct nozzle is properly installed in the burner as shown in the preliminary burner settings and that the burner electrode are adjusted as per the oil burner manual.

When using the Beckett AFG oil burner on the three or four section boiler, the opening in the refractory on the door must be enlarged to insert the oil burner without damaging the door refractory. Use a sharp utility knife to carefully trim the opening to size.

The oil burner when properly installed will extend beyond the refractory liner of the burner door. Riello - will extend approximately 2” beyond the refractory on the swing door.

HeatWise - will extend approximately 3” beyond the refractory on the swing door. Beckett AFG - will extend approximately 4-1/8” beyond the refractory on the swing door. Beckett NX - will extend approximately 2-3/4” beyond the refractory on the swing door.

Check that there is a complete seal between the door and the burner flange after installing ceramic fiber seal furnished with the burner.

Place burner Installer/Serviceman label on boiler jacket front panel as required.

Image 15
Contents SL375 Thru SL7175 Be Aware of Hazard Definitions Table of Contents Ratings and Data Ventilation and Combustion Air Installation ClearancesPackaged Boiler is Shipped in TWO Packages Boiler AssemblyBoiler Trim Piping Temperature Controls Installation and AdjustmentJacket installation Expansion Tanks System PipingLow water cut off Relief ValvesChimney VentingChimney Connector Direct Venting Combination AIR INTAKE/VENT System Page Direct Vent OIL Burners Burner InstallationOil Tank and Piping Electrical WiringPage Page Operation Swing DoorBurner Adjustments Start-UpStart-up Equipment Control Circuit Safety Checks Preliminary Burner SettingsOil Burner MaintenanceOil Filter BoilerVent System Domestic Hot Water Storage TankBurner Will Not Start Trouble Shooting GuideBurner Goes Off On Safety Page Solaia Residential Cast Iron Boiler Warranty Installation and Service Check List Warranty Registration Page