Thomas & Betts RZ-NA 441-OMS Temperature Limit Safety Controls contd, Air Pressure Switches

Page 6
Figure 11 - ECO
Limit Control, P/N 82414
Setting 305oF

8.Temperature Limit Safety Controls (cont'd)

Emergency Cut Off Limit Control

Function: The emergency cut off is a fus- ible link high temperature limit which pro- vides one-time redundant protection against overheating. If the temperature sensitive limit control malfunctions, the electrically activated emergency cutoff will shutdown the system.

Service: If this limit activates, the manual limit control has failed and must be re- placed. The cause for activating the emer-

gency cut off limit control must be found and corrected before re- starting the system.

9. Air Pressure Switches

Location: Control Compartment Electrical Box (See Figure 7.) Depending on the options selected, there are two or four switches.

Figure 12 - Air

Pressure Switch

Attach a slope gauge (0 to 1.0" scale) to the tubing connections in the control compartment. The two connections are located below the elec- trical control box. Remove the caps on the 1/8" NPT test connections and attach the slope gauge. (The recommended method for attaching the slope gauge is to use field-supplied 1/8" female NPT x 1/4" O.D. barbed hose connections.)

A)If the system includes an optional discharge damper, before measur- ing burner differential air pressure, check to be sure that the damper is fully open.

B)With the blower operating, the pressure differential on the slope gauge should read between -.5" and -.7" w.c. If the slope gauge reading is within those limits, no adjustments are necessary.

If the slope gauge reading is not within the setpoint limits of the air flow switches (.2" to .9" w.c.), and the system is operating, replace the air pressure switch(es).

If the slope gauge reading is not between -.5" and -.7" w.c., but within the setpoint limits, clean the sensing tubes (Follow the in- structions in Maintenance Section, Paragraph 4).

C)When air pressure is within the proper range, turn the disconnect switch OFF. Disconnect the manometer and the slope gauge. Re- place the caps removed to connect the slope gauge.

Service: If the pressure check determines that an air flow switch is not functioning properly, the switch cannot be serviced and must be re- placed with an identical replacement. Low air pressure switch is P/N 86986; high air pressure switch is P/N 86987; bypass damper switches, P/N 87249 (normally closed, set to open at .5" w.c.) or P/N 87250 (normally open, set to close at .65" w.c.).

• Low Air Flow Switch

Function: The low air flow switch is a velocity pressure switch that monitors air flow across the burner. Until the air flow attains adequate volume for combustion, the switch remains open. When the switch recognizes adequate air volume, it closes, permitting both the pilot and burner to operate. Low pressure switch is normally open; it closes on pressure rise at .2" w.c. Do not alter or adjust setting.

• High Air Flow Switch

Function: The high air flow switch is a velocity pressure switch that monitors air flow across the burner. If the high air flow switch senses air velocity above the prescribed limit, it will shutdown gas flow to the burner. High pressure switch is normally closed; it opens when pres- sure rises above .9" w.c. Do not alter or adjust setting.

Bypass Damper Air Flow Switches (systems with Air Control Options AR19, AR20, AR22, AR23, AR32, AR33, AR34, AR36, or AR37)

Function: With a bypass damper, the volume of outside air supplied

to the building is adjusted by a manually set potentiometer (Option AR19 and AR22) or automatically by a pressure null switch (Option AR20 or AR23), a photohelic pressure switch (Option AR36 or AR37), or a field-supplied computer signal (Option AR33 or AR34). With Options AR19, AR20, AR33, and AR36 the supply air is varied by adjusting the position of a damper at the blower discharge. With Op- tions AR22, AR23, AR34, and AR37, a return air damper is adjusted to vary the volume of return air. The unit is arranged so that a fixed amount (20%) of the rated volume flows over the burner at a constant velocity. The remainder (80%) of the rated air volume flows either through a balancing bypass damper or a combination of bypass and return air dampers. As the supply air volume is varied by the return air or dis- charge damper, the balancing damper is adjusted to maintain the re- quired air velocity over the burner. Adjustment of the bypass damper is controlled by the bypass damper pressure switches. One pressure switch is normally closed with a setting of .5" w.c.; the other is nor- mally open with a setting of .65" w.c. balancing bypass damper.

Sensing Pressure Check: (requires a slope gauge, several feet of

1/4" O.D. tubing and two 1/4" O.D. barbed tees.)

Page 6

10. Ignition System

Location: Ignition Controller Module in the Control Compartment Electrical Box (See Figures 7 and 13.); Ignitor and Flame Sensor on the Burner (See Figure 14.)

Figure 13 - Ignition Control

Figure 14 - Ignitor, P/N

Module in the Electrical

121865, and Flame

Compartment, P/N 157953

Sensor, P/N 134706, on

 

the Burner

 

Sensor

Ignitor

Hot Surface Ignition System with Prepurge Time Delay and Flame Sensor with 100% Lockout

Function: The ignition system including the controller, the hot surface ignitor, and the flame sensor function to ignite and prove the pilot flame. When there is a call for heat, the modular ignition controller is energized. When the controller reads 1.4 amps going to the hot surface ignitor, it opens the pilot valve for a 15-second trial for ignition. After the pilot flame rod senses pilot flame, the main gas valve is energized. If the pilot flame rod does not sense a pilot flame, the controller shuts down the pilot valve for a 10-second interpurge and then opens it again for a second ignition trial. If pilot flame is not proven on the second trial, the ignition controller locks out and must be manually reset by an interruption of the main circuit (disconnect switch).

Service: The modular ignition controller does an internal self-check each time that it is energized and will lockout if not found to be func-

Image 6
Contents Operating/Maintenance/Service Instructions Table of ContentsMaintenance Section Maintenance Schedule1B. Blower Belts Drive Components1A. Blower Bearings 2. FiltersCircuit Indicator Board check lights Main Burner and Pilot AssemblyAir Pressure Temperature Limit Safety Controls Controls Location, Operation, and ServiceElectronic Circuit Board with Diagnostic Lights Manual Reset Limit Control BlowerTemperature Limit Safety Controls contd Air Pressure SwitchesIgnition System Direct-Fired Burner Electronic Modulation Gas Control Option AG37Selector, P/N Gas Pressure Switches Manifold ArrangementsCutoff Control Door Switch Option BX1 required on C.G.A.-certified units Inlet Air ControlsPhotoelectric Smoke Detector Option SA1 Dirty Filter SwitchInlet Air Controls contd Firestat Option BD5Troubleshooting Contact Troubleshooting contdContact the Installer Index

RZ-NA 441-OMS specifications

The Thomas & Betts RZ-NA 441-OMS is a cutting-edge component designed for advanced electrical applications, known for its reliability and performance. This product stands out in the market due to its innovative features and robust design, making it ideal for a variety of industrial and commercial uses.

One of the main features of the RZ-NA 441-OMS is its superior connectivity capabilities. The component is engineered to provide seamless integration with multiple electrical systems, ensuring efficient power distribution and minimal downtime. The versatility of this device enables it to be utilized in various setups, including complex machinery and sophisticated automation processes.

Another notable characteristic of the RZ-NA 441-OMS is its remarkable insulation properties. The device is built with high-quality materials that enhance its thermal stability and resistance to environmental factors. This ensures that it can withstand harsh conditions while maintaining optimal functionality, making it a reliable choice for outdoor applications and areas with extreme temperatures.

The RZ-NA 441-OMS also incorporates advanced safety features, such as overcurrent protection and fault detection systems. These technologies are designed to prevent electrical failures, safeguarding both the equipment and personnel involved. This emphasis on safety aligns with Thomas & Betts’ commitment to providing reliable solutions that prioritize user protection and system integrity.

In terms of installation, the RZ-NA 441-OMS is designed for ease of use. Its compact design allows for quick and straightforward mounting, saving valuable time during setup. Additionally, it features customizable configurations, making it suitable for various application needs. This flexibility is particularly beneficial for companies seeking to optimize their operations while ensuring compatibility with existing infrastructure.

Moreover, the RZ-NA 441-OMS is supported by extensive documentation and customer service, ensuring that users have access to the information and assistance they need for effective implementation and troubleshooting.

Overall, the Thomas & Betts RZ-NA 441-OMS represents a significant advancement in electrical connectivity solutions, combining robustness, versatility, and safety in a single package. Its innovative features make it an essential component for businesses looking to enhance their electrical systems reliably and efficiently.