3. Disconnect closed, blower switch in test position, | 1. | Freezestat option not ordered - verify order/wiring diagram. |
"firestat" light is lit, but "freezestat" light is not lit | 2. | Freezestat relay contacts are open - checking setting on control. |
| 3. | Indicator bulb is burned out - replace bulb (P/N 125189). |
| | |
4. Disconnect closed, blower switch in test position, "firestat" and | 1. | End switch on damper motor not closed. - check end switch wiring. |
"freezestat" lights are lit, but "starter energized" light is not lit | 2. | Faulty damper relay - replace relay. |
and the blower motor is not operating. | 3. | Damper motor miswired - rewire damper motor per wiring diagram. |
| | |
5. Disconnect closed, blower switch in test position, | 1. | Blower motor not wired correctly - check wiring diagram on motor. |
"firestat", "freezestat" and "starter energized" | 2. | Faulty motor starter - replace (check coil first). |
lights are lit, but the blower motor is not operating. | 3. | Faulty blower motor relay - replace relay. |
6. Disconnect closed; blower switch in test position; "firestat", | 1. | Low air switch open - verify pressure drop at burner. |
"freezestat" and "starter energized" lights are lit and the | 2. | Indicator light is burned out - replace bulb (P/N 125189). |
blower motor is operating; but the "low air light" is not lit. | 3. | Faulty low air switch - replace pressure switch (P/N 86986). |
7. Disconnect closed; blower switch in test position; | 1. | High air switch open - verify pressure drop at burner. |
"firestat", "freezestat", "starter energized" and "low | 2. | Indicator light is burned out - replace bulb (P/N 125189). |
air" lights are lit and the blower motor is operating; | 3. | High air switch option not ordered - verify order/wiring diagram. |
but the "high air light" is not lit. | 4. | Faulty high air switch - replace pressure switch (P/N 86987). |
8. Disconnect closed; blower switch in test position; "firestat", | 1. | Indicator light is burned out - replace bulb (P/N 125189). |
"freezestat", "starter energized", "low air" and "high air" | 2. | Tripped manual reset limit control(s) - reset manual control. |
are lit; but the "limit control normal" light is not lit. | 3. | Faulty manual limit control (s) - replace limit control. |
9. Disconnect closed; blower switch in test position; | 1. | Indicator light is burned out - replace bulb (P/N 125189). |
"firestat", "freezestat", "starter energized", "low air", | 2. | High ambient control option not ordered - verify order/wiring diagram. |
"high air" and "limit control normal" lights are lit; | 3. | High ambient control contacts open - check setting on control. |
but the "ambient (outside air) cutoff normal" light is not lit. | | |
| | |
10. Disconnect closed; blower switch in test position; | 1. | Indicator light is burned out - replace bulb (P/N 125189). |
"firestat", "freezestat", "starter energized", "low air", | 2. | Low gas pressure switch option not ordered - verify order/wiring diagram. |
"high air", "limit control normal" and "ambient (outside air) | 3. | Low gas pressure switch contacts open - check setting on control. |
cutoff normal" lights are lit; but the "low gas | 4. | Low gas pressure switch contacts open - check gas pressure. |
pressure normal" light is not lit. | 5. | Faulty gas pressure switch - replace gas pressure switch. |
11. Disconnect closed; blower switch in test position; | 1. | Indicator light is burned out - replace bulb (P/N 125189). |
"firestat", "freezestat", "starter energized", "low air", | 2. | High gas pressure switch option not ordered - verify order/wiring diagram. |
"high air", "limit controls normal", "ambient (outside air) | 3. | High gas pressure switch contacts open - check setting on control. |
cutoff normal" and "low gas pressure normal" lights are lit; | 4. | High gas pressure switch contacts open - check gas pressure. |
but the "high gas pressure normal" light is not lit. | 5. | Manual reset on switch tripped - reset pressure switch manual reset. |
| 6. | Faulty gas pressure switch - replace gas pressure switch. |
| | |
12. Disconnect closed; blower and burner switches in run | 1. | Lack of power at L1 on ignition module - ECO blown, find |
position; control switch is in "winter" position; | | cause then replace ECO. |
"control power", "high gas normal"; "low gas normal"; | 2. | Faulty burner enable relay - replace relay. |
"firestat normal"; "system switch energized"; "starter | 3. | Low stage relay contacts are not closed - check air controller or |
energized" and "freezestat normal" lights are lit; but | | thermostat setting. |
ignitor is not becoming energized or beginning to glow. | 4. | Faulty low stage relay - replace relay. |
| 5. | Faulty hot surface ignitor - check continuity at the ignition module |
| | and circuit board. If reading is greater than 5-6 ohms, replace ignitor. |
| 6. | Faulty ignition module - replace entire module. |
13. Disconnect closed; blower and burner switches in run | 1. | Ignitor not reaching 1.4A threshold - check voltage and |
position; control switch is in "winter" position; "control power", | | current to ignitor. |
high gas normal; "low gas normal"; "firestat normal"; "system | 2. | Faulty hot surface ignitor - check continuity, replace ignitor. |
switch energized"; "starter energized" and "freezestat normal" | 3. | Faulty ignition module - replace entire module. |
lights are lit; ignitor glowing but "pilot valve normal" light | | |
(thus the pilot valve) is not energized. | | |
| | |
| | Page 11 |