Thomas & Betts RZ-NA 441-OMS installation manual Troubleshooting

Page 11

19. Troubleshooting

Chart 1 - General Troubleshooting Guide (Check the diagnostic lights on the circuit board)

Symptom or Problem

Cause and Remedy

1. Disconnect switch is closed, but "control power" light is not lit.

1. Fuses are missing or blown in disconnect switch - replace fuses.

2.Transformer not wired according to diagram - check wiring.

3.Secondary 8A fuse (on transformer) is missing or blown - replace fuse.

4.Indicator light is burned out - replace bulb (P/N 125189).

2.Disconnect switch is closed, but "firestat normal" light is not lit. 1. See causes and remedies for Problem 1 above.

2.Optional control relay or door switch contacts are open - to test, jump terminals 3 to 4 or 1 to 2.

3.Firestat option not ordered - verify order/wiring diagram.

4.Firestat manual reset tripped - reset firestat control.

3. Disconnect closed, blower switch in test position,

1.

Freezestat option not ordered - verify order/wiring diagram.

"firestat" light is lit, but "freezestat" light is not lit

2.

Freezestat relay contacts are open - checking setting on control.

 

3.

Indicator bulb is burned out - replace bulb (P/N 125189).

 

 

 

4. Disconnect closed, blower switch in test position, "firestat" and

1.

End switch on damper motor not closed. - check end switch wiring.

"freezestat" lights are lit, but "starter energized" light is not lit

2.

Faulty damper relay - replace relay.

and the blower motor is not operating.

3.

Damper motor miswired - rewire damper motor per wiring diagram.

 

 

 

5. Disconnect closed, blower switch in test position,

1.

Blower motor not wired correctly - check wiring diagram on motor.

"firestat", "freezestat" and "starter energized"

2.

Faulty motor starter - replace (check coil first).

lights are lit, but the blower motor is not operating.

3.

Faulty blower motor relay - replace relay.

6. Disconnect closed; blower switch in test position; "firestat",

1.

Low air switch open - verify pressure drop at burner.

"freezestat" and "starter energized" lights are lit and the

2.

Indicator light is burned out - replace bulb (P/N 125189).

blower motor is operating; but the "low air light" is not lit.

3.

Faulty low air switch - replace pressure switch (P/N 86986).

7. Disconnect closed; blower switch in test position;

1.

High air switch open - verify pressure drop at burner.

"firestat", "freezestat", "starter energized" and "low

2.

Indicator light is burned out - replace bulb (P/N 125189).

air" lights are lit and the blower motor is operating;

3.

High air switch option not ordered - verify order/wiring diagram.

but the "high air light" is not lit.

4.

Faulty high air switch - replace pressure switch (P/N 86987).

8. Disconnect closed; blower switch in test position; "firestat",

1.

Indicator light is burned out - replace bulb (P/N 125189).

"freezestat", "starter energized", "low air" and "high air"

2.

Tripped manual reset limit control(s) - reset manual control.

are lit; but the "limit control normal" light is not lit.

3.

Faulty manual limit control (s) - replace limit control.

9. Disconnect closed; blower switch in test position;

1.

Indicator light is burned out - replace bulb (P/N 125189).

"firestat", "freezestat", "starter energized", "low air",

2.

High ambient control option not ordered - verify order/wiring diagram.

"high air" and "limit control normal" lights are lit;

3.

High ambient control contacts open - check setting on control.

but the "ambient (outside air) cutoff normal" light is not lit.

 

 

 

 

 

10. Disconnect closed; blower switch in test position;

1.

Indicator light is burned out - replace bulb (P/N 125189).

"firestat", "freezestat", "starter energized", "low air",

2.

Low gas pressure switch option not ordered - verify order/wiring diagram.

"high air", "limit control normal" and "ambient (outside air)

3.

Low gas pressure switch contacts open - check setting on control.

cutoff normal" lights are lit; but the "low gas

4.

Low gas pressure switch contacts open - check gas pressure.

pressure normal" light is not lit.

5.

Faulty gas pressure switch - replace gas pressure switch.

11. Disconnect closed; blower switch in test position;

1.

Indicator light is burned out - replace bulb (P/N 125189).

"firestat", "freezestat", "starter energized", "low air",

2.

High gas pressure switch option not ordered - verify order/wiring diagram.

"high air", "limit controls normal", "ambient (outside air)

3.

High gas pressure switch contacts open - check setting on control.

cutoff normal" and "low gas pressure normal" lights are lit;

4.

High gas pressure switch contacts open - check gas pressure.

but the "high gas pressure normal" light is not lit.

5.

Manual reset on switch tripped - reset pressure switch manual reset.

 

6.

Faulty gas pressure switch - replace gas pressure switch.

 

 

 

12. Disconnect closed; blower and burner switches in run

1.

Lack of power at L1 on ignition module - ECO blown, find

position; control switch is in "winter" position;

 

cause then replace ECO.

"control power", "high gas normal"; "low gas normal";

2.

Faulty burner enable relay - replace relay.

"firestat normal"; "system switch energized"; "starter

3.

Low stage relay contacts are not closed - check air controller or

energized" and "freezestat normal" lights are lit; but

 

thermostat setting.

ignitor is not becoming energized or beginning to glow.

4.

Faulty low stage relay - replace relay.

 

5.

Faulty hot surface ignitor - check continuity at the ignition module

 

 

and circuit board. If reading is greater than 5-6 ohms, replace ignitor.

 

6.

Faulty ignition module - replace entire module.

13. Disconnect closed; blower and burner switches in run

1.

Ignitor not reaching 1.4A threshold - check voltage and

position; control switch is in "winter" position; "control power",

 

current to ignitor.

high gas normal; "low gas normal"; "firestat normal"; "system

2.

Faulty hot surface ignitor - check continuity, replace ignitor.

switch energized"; "starter energized" and "freezestat normal"

3.

Faulty ignition module - replace entire module.

lights are lit; ignitor glowing but "pilot valve normal" light

 

 

(thus the pilot valve) is not energized.

 

 

 

 

 

 

 

Page 11

Image 11
Contents Table of Contents Operating/Maintenance/Service InstructionsMaintenance Schedule Maintenance Section2. Filters Drive Components1A. Blower Bearings 1B. Blower BeltsAir Pressure Circuit Indicator Board check lightsMain Burner and Pilot Assembly Manual Reset Limit Control Blower Controls Location, Operation, and ServiceElectronic Circuit Board with Diagnostic Lights Temperature Limit Safety ControlsIgnition System Temperature Limit Safety Controls contdAir Pressure Switches Selector, P/N Direct-Fired BurnerElectronic Modulation Gas Control Option AG37 Cutoff Control Gas Pressure SwitchesManifold Arrangements Inlet Air Controls Door Switch Option BX1 required on C.G.A.-certified unitsFirestat Option BD5 Dirty Filter SwitchInlet Air Controls contd Photoelectric Smoke Detector Option SA1Troubleshooting Index Troubleshooting contdContact the Installer Contact

RZ-NA 441-OMS specifications

The Thomas & Betts RZ-NA 441-OMS is a cutting-edge component designed for advanced electrical applications, known for its reliability and performance. This product stands out in the market due to its innovative features and robust design, making it ideal for a variety of industrial and commercial uses.

One of the main features of the RZ-NA 441-OMS is its superior connectivity capabilities. The component is engineered to provide seamless integration with multiple electrical systems, ensuring efficient power distribution and minimal downtime. The versatility of this device enables it to be utilized in various setups, including complex machinery and sophisticated automation processes.

Another notable characteristic of the RZ-NA 441-OMS is its remarkable insulation properties. The device is built with high-quality materials that enhance its thermal stability and resistance to environmental factors. This ensures that it can withstand harsh conditions while maintaining optimal functionality, making it a reliable choice for outdoor applications and areas with extreme temperatures.

The RZ-NA 441-OMS also incorporates advanced safety features, such as overcurrent protection and fault detection systems. These technologies are designed to prevent electrical failures, safeguarding both the equipment and personnel involved. This emphasis on safety aligns with Thomas & Betts’ commitment to providing reliable solutions that prioritize user protection and system integrity.

In terms of installation, the RZ-NA 441-OMS is designed for ease of use. Its compact design allows for quick and straightforward mounting, saving valuable time during setup. Additionally, it features customizable configurations, making it suitable for various application needs. This flexibility is particularly beneficial for companies seeking to optimize their operations while ensuring compatibility with existing infrastructure.

Moreover, the RZ-NA 441-OMS is supported by extensive documentation and customer service, ensuring that users have access to the information and assistance they need for effective implementation and troubleshooting.

Overall, the Thomas & Betts RZ-NA 441-OMS represents a significant advancement in electrical connectivity solutions, combining robustness, versatility, and safety in a single package. Its innovative features make it an essential component for businesses looking to enhance their electrical systems reliably and efficiently.