York K3EU180A50 Installation, Limitations, Location, Clearances, Rigging and Handling

Page 2

035-12124-000 Rev. A (0501)I

INSTALLATION

LIMITATIONS

These units must be installed in accordance with applicable na- tional, local and municipal safety codes.

If components are to be added to a unit to meet local codes, they are to be installed at the dealer's and/or the customer's -ex pense. Refer to Table 2 for Unit Application Data.

LOCATION

This blower unit is not designed for outdoor installation. It must be located within the building structure, either inside or outside the conditioned space.

The unit should be located as close to the condensing unit as practical and positioned to minimize bends in the refrigerant piping.

Units being installed vertically or horizontally can be set directly on a floor or platform, or they can be supported by metal or wooden beams.

Units being installed horizontally can also be suspended from above. Refer to the suspension accessory instruction installa- tion procedures.

CLEARANCES

The clearances listed on the unit dimension drawing (Figure 7) are required for the proper service and operation of the unit.

RIGGING AND HANDLING

Be careful when moving the unit. Do not remove any packaging until the unit is near its final location.

The packaging consists of a bottom wooden skid that can be lifted with a fork truck from any direction, a clear heavy mil bag that covers the entire unit, and strapping that secures the clear bag to the bottom of the skid.

These units can be rigged with slings under the bottom skid.

CAUTION: Spreader bars should be used to prevent slings from crushing the unit panels and frame.

Before rigging any unit, determine its weight from Table 1. Bef- ore rigging a unit for horizontal installation, make sure that its weight will be distributed equally.

Table 1 - PHYSICAL DATA

 

 

Rows Deep

4

 

 

 

 

 

 

 

Rows High

26

 

 

 

 

 

Evaporator Coil

Finned Length (in./mm)

54.5/1384

 

 

 

Fin/Inch

13

 

 

 

 

 

 

 

 

 

Tube O.D. (in./mm)

3/8/9.6

 

 

 

 

 

 

 

Face Area (Ft.2/m2)

12.4/1.15

Centrifugal

Wheel Dia. x Width

inches

18 x 18

Blower1

mm

457 x 457

 

 

 

 

 

 

 

 

 

 

 

inches

20 x 20 x1

Filters

2

Size

 

 

mm

508 x 508

 

 

(6 Req'd)

 

x 25

 

 

 

 

 

 

 

 

 

Face Area (Ft.2/m2)

16.7/1.5

Operating Charge ( Refrigerant 22) (Lbs/Kg)

5.5/2.5

 

 

 

 

 

Weight (Lbs/Kg)

Shipping

480/218

 

 

 

Operating

440/200

 

 

 

 

 

 

 

 

 

 

10 kW

63/28.5

 

 

 

 

 

 

 

Electric Heaters

16 kW

66/29.9

 

 

 

 

 

 

26 kW

71/32.2

 

 

 

 

 

 

 

 

 

 

 

36 kW

74/33.5

 

 

 

 

 

Accessory

Supply Air Plenum

144/65

 

 

 

Weights(Lbs/Kg)

Base

65/29

 

 

 

 

 

 

 

 

 

Return Air Grille

19/9

 

 

 

 

 

 

 

Horizontal Suspension

68/31

 

 

 

 

 

 

 

Steam Coil

149/68

 

 

 

 

 

 

 

Hot Water Coil

135/61

1Refer to data in Table 7 for complete motor specifications.

2Filters are throwaway type. Two inch (50mm) filters may be used, if required by removing the 1" (25mm) filter retaining angles provided in the filter rack.

TABLE 2 - UNIT APPLICATION DATA

 

 

Voltage

Supply Air Range

 

Entering Air Temperature, °F(°C)

Power

 

Variation*

CFM/m3s

Cooling-db/wb

 

Heating-db

Supply

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Min.

 

Max.

Min.

Max.

Min.

 

Max.

Min.

 

Max.

380/415-3-50

342

 

457

4800/2.26

7200/3.40

68/57 (20/14)

 

86/72 (30/22)

-

 

77 (25)

*Utilization Range “A” in accordance with ARI Standard 110.

2

Unitary Products Group

Image 2
Contents Reference Sunline SPLIT-SYSTEMGeneral InspectionLocation InstallationLimitations ClearancesVertical and Horizontal Application VERTICAL/HORIZONTAL InstallationInstalling Refrigerant Mains Duct ConnectionsDrain Connection Supply AIR Blower AdjustmentSupply AIR Blower Motor Pulley Adjustment Expansion Valve BulbPressure Drop VS Supply Airflow Electrical Data Typical Motor Mounting AssemblyHole Locations FLA LRAAccessory Static Resistance IWG Blower PerformanceUnit Unit Dimensions and ClearancesAccessories Electric Heater Supply AIR PlenumMotor Specifications MaintenancePower and Control Wiring Blower Motor and Drive Data