Schneider Electric ION8800 Wire the Power Supply, Power Up the Meter, Single Phase Power Supply

Page 22

Step 5: Wire the Power Supply

ION8800 meter power supply connections are found on the Essailec connector.

Single Phase Power Supply

Fuse for N/- terminal required if neutral is ungrounded.

Rated Inputs

85 - 240 VAC ±10% (47 - 63 Hz)

110 - 270 VDC ±10%

 

 

 

Rating

Installation category II (local), Pollution degree 2

Dielectric Withstand

2,000 VAC RMS for 60s (50Hz)

 

 

Max. Burden

9 W (20 VA) for base unit without comm module

 

 

 

Min: 120 ms (6 cycles @ 50 Hz)

Ride-through

Typical: 0.5 - 5 s (depending on input voltage and

 

configuration)

 

 

Step 6: Power Up the Meter

DANGER

Before you apply power to the meter, ensure that ground is securely connected and that the supply voltage is within the allowed range of the meter’s power supply.

Step 7: Set Up the Meter Using the Front Panel

The following Setup screens are available for meter configuration via the front panel:

BASIC SETUP

DEMAND SETUP

COM1 SETUP

COM2 SETUP

COM3 SETUP

COM4 SETUP

NETWORK SETUP

FORMAT SETUP

DISPLAY SETUP

SECURITY SETUP

The following example shows Volts Mode setup using the meter front panel.

Press and hold

Press

Press

Press

Press

Press ALT/ENTER and

Use arrow buttons to

Use arrow buttons to

Use arrow buttons to

hold for 3 seconds to

move up and down in

move up and down in

move up and down in

enter Setup Mode

list. Press ALT/ENTER to

list. Press ALT/ENTER to

list. Press ALT/ENTER to

from Display Mode.

select Basic Setup.

select Volts Mode.

select 4W-WYE.

22

© 2007 Schneider Electric. All rights reserved.

Image 22
Contents PowerLogic ION8800 Energy & Power Quality MeterPage Installation Considerations Network Compatibility Notice for the Internal Modem Standards ComplianceAvailable Options ION8800 ModelsBefore You Begin OptionsMeter Front Cover Open Meter OverviewMeter Front Cover Closed Meter BackFront of Meter Cover Closed Meter LabelsFront Panel Button Functions Removable User LabelsSide View of Meter Unit DimensionsFront of Rack View Order Options B/C Circuit & Pinout Diagrams Essailec ConnectionsOrder Option a Circuit & Pinout Diagrams Order Options A/B/C Essailec Connector Arrangement Meter Port Essailec Connector Pin DescriptionOrder Options D/E Circuit & Pinout Diagrams Meter Battery Considerations Order Options D/E Essailec Connector ArrangementMount the Meter Environmental Specifications IEC62052-11 InstallationForm C Digital Output Solid State Relay Outputs DO1 DO4 Wire the Digital I/OForm C Digital Output Mechanical Alarm Relay Form a Digital Outputs Solid State Relay Outputs DO5 DO12Current Inputs High Current Option Wire the Voltage and Current InputsVoltage Inputs Current Inputs Low Current OptionWire Wye, 2½-Element, 2 PTs Connection Wire Wye, 3-Element, Direct Connection DiagramWire Wye, 3-Element, 3 PTs Connection Diagram L-N / 500 V L-L max. Volts Mode = 4W-WyeWire Delta, 2-Element 2 PTs & 2 CTs Wire Solid-Grounded Wye, 3-Element, Direct ConnectionWire Delta, 2½-Element, Direct Connection L-L max. Volts Mode = DeltaSingle Phase Connection Diagram Wire Delta, 2½-Element, 2 PTs & 3 CTsUsing Potential Transformers Infrared Connections COM1 Wire the CommunicationsWire Null modem RS-232 cable RS-485 Connections COM2 and COM3Internal Modem Connection COM4 optional module Ethernet TCP/IP Service PortsEthernet Connections optional module 10Base-TSet Up the Meter Using the Front Panel Wire the Power SupplyPower Up the Meter Single Phase Power Supply4W-WYE Setup Menu Setting Description Range Values DefaultNetwork Format LD/LG, +/-, CAP/INDApplicable Volts Mode = Delta Phasor DiagramsDelta phasors for Unity Power Factor resistive load Verify Meter OperationWYE 123 Rotation Applicable Volts Mode = 4W-WYE and 3W-WYEWYE 132 Rotation Element 3Wire Delta 123 Rotation Element 3Wire Delta 132 RotationPer-phase voltage harmonic histograms Norm modeALT mode Per-phase current harmonic histogramsTest Mode Meter always returns to Norm mode after exiting Test modeBattery Dimensions Replacing the BatteryBattery Specifications To replace the batteryAnti-Tamper Sealing Methods Meter SecurityHardware Locked Security Option Meter SealsFront of Meter Front Panel Sealing Point Cover Sealing Point Schneider Electric. All rights reserved Page ION8800 Schneider Electric

ION8800 specifications

The Schneider Electric ION8800 is an advanced power monitoring and management device designed for commercial and industrial applications. It is engineered to enhance energy efficiency, reduce operational costs, and improve the reliability of electrical systems. As part of Schneider Electric's ION series, the ION8800 stands out due to its sophisticated metering capabilities and robust communication features.

One of the main features of the ION8800 is its high-accuracy power measurement. The device is capable of measuring a wide array of electrical parameters, including voltage, current, power, and energy consumption. With its accurate metering capabilities, operators can identify inefficiencies and optimize energy usage, thereby contributing to sustainability goals.

The ION8800 integrates with Schneider Electric's EcoStruxure™ platform, allowing seamless connectivity and data accessibility. This integration enables users to monitor their power systems remotely, gaining insights through real-time data visualization. Users can access detailed reports and analytics that help them to make informed decisions about energy management and equipment reliability.

In addition to its metering capabilities, the ION8800 incorporates advanced communication technologies. It supports multiple protocols, including Modbus, DNP3, and IEC 61850, ensuring compatibility with various industrial automation systems. This flexibility makes it suitable for integration in diverse applications and installations.

Another notable characteristic of the ION8800 is its scalability. The device can accommodate the growing needs of an organization, from single-entity monitoring to a larger network of devices. This scalability allows businesses to start with a basic setup and expand their monitoring capabilities as their energy management requirements evolve.

The ION8800 is designed to withstand harsh industrial environments, featuring durable construction and compliance with global standards. This resilience ensures reliability and longevity in various operational conditions. Additionally, the device’s user-friendly interface allows for easy configuration and operation, reducing the learning curve for new users.

Overall, the Schneider Electric ION8800 is a versatile and powerful tool for improving energy efficiency and management in commercial and industrial settings. Its advanced features, robust communication technologies, and scalability make it a valuable asset for businesses looking to enhance their energy monitoring capabilities. As companies increasingly focus on sustainability, the ION8800 provides the insights and tools necessary for effective energy management.