Installation / Initial Set-Up

3. Set-up either as a BUILDING BACK-UP or PORTABLE Power Source

This generator is designed to provide up to 13,000W of electrical power. It can supply electricity in two ways:

1.As a back-up, standby power source for a building. For this application, you must arrange for a licensed electrician to connect the generator to your building’s electrical system via the installation of an UL-approved transfer switch. The transfer switch must be installed in accordance with building electrical code and guidelines supplied by your power company.

2.As a portable power source. You can plug appliances or tools directly into the generator’s electrical outlets.

Specific requirements for each are given below.

Note: Regardless of whether you use your generator as a back-up power source connected to a building or as a portable power source, you must not overload the generator. Overloading may cause serious damage to the generator and attached electrical devices.

Using as a Back-up Power Source for a Building

Contact a licensed electrician to install a UL-approved transfer switch if you want to use your generator as a back-up power source for a building.

What does a transfer switch do? It:

a)Safely connects the generator to your building’s electrical system by isolating your generator from your utility company’s power lines,

AND

b)Connects your generator to a critical subset of your building’s circuits that are needed for emergency power needs.

If your generator will be connected to your building’s electrical system, it MUST ALWAYS be isolated from the utility power grid with a UL-approved transfer switch installed by a licensed electrician in compliance with all applicable building and electrical codes, and in accordance with guidelines supplied by your power company.

DANGER:

A transfer switch must be installed in order to isolate your generator from the utility power grid. If your generator is NOT properly isolated from the utility system, serious hazards will arise:

When your generator is running, it’s output will back feed into the utility power line and transformer that are normally used to provide you with power. The transformer will step up the current to the normal line voltage. An unsuspecting utility line worker working on what he thinks is a deactivated line could be electrocuted.

If your generator is connected (running or not) when utility power is restored, your generator will be destroyed. It could also explode or cause fire.

In addition to isolating your generator from the utility system, the transfer switch connects your generator to a limited set of circuits in your building that have been chosen as critical to operate during a power outage.

13

Image 13 Contents
10,500 Watt Continuous 13,000 Watt Surge Capacity Any Questions, Comments, Problems, or Parts OrdersHazard Signal Word Definitions Table of Contents About Your Generator About Your GeneratorAbout Your Generator cont’d Warranty RegistrationSpecifications Item #165923 SpecificationsPart numbers Description Safety Label Locations Item #165923V.1Description Machine Component Identification Item #165923V.1 Reference Guide Example conversion to watts Power Load Planning & ManagementTotal 6275W Power Load Planning & Management cont’dPlanning the Power Load Installation / Initial Set-UpUnpacking & Delivery Inspection Set-up either as a Building BACK-UP or Portable Power Source 13000 PPG Current/Power Maximum Extension Cord Length Select a Suitable Site Installation / Initial Set-Up Grounding the generator Battery Installation Operation General safety rules for operationOperation cont’d Static electricity and filling the gasoline tank Manual Preparing for OperationOperation cont’d Inspect Fuel System / Check for Leaks Personal Protection Starting the Engine Checking Generator Output Stop the engine using the following steps Connecting LoadsStopping Storage & Exercise Store the generator in a location that is o Clean and dryOperation cont’d Maintenance & Repair Maintenance & RepairMaintenance & Repair cont’d Troubleshooting TroubleshootingSafety Installation & Set-up Summary of Important Safety Information for OperationBattery Safety GeneralInstallation / Initial Set-up Safety Safety Before UseKnow how to operate Personal protective equipmentGasoline Safety Safety During UseSafety Inspection/Maintenance Safety After useGenerator Exploded View Rev Diag # Description Qty Wiring Diagram Rev Diag # Description Qty Ref # Description Qty Generator Head Exploded View Rev