S6065A1003/2001 LIQUID FLOW SWITCHES

SWITCH-POINT ADJUSTMENT

The flow switch is factory-set to the min. flow rate. To adjust the device to other levels, turn the adjustment screw clockwise. Table 1 lists the reset points and switch points for water. Data for other media must be determined empirically.

NOTE: If the flow switch is used as a min. flow controller, another device must be installed downstream for alarm condition activation.

DIMENSIONS

Table 1. Reset and switch points for water

 

paddles (L)

 

 

pipe Ø

 

 

rec. Qmax

 

reset / switch point

 

 

 

 

 

 

min. flow

max. flow

 

 

 

 

 

3

 

 

 

 

 

 

 

 

(m /h)

 

(m3/h)

(m3/h)

1"

 

1"

 

3.6

 

0.6 / 1.0

2.0 / 2.1

1"

 

1-1/4"

 

6.0

 

0.8 / 1.3

2.8 / 3.0

1"

 

1-1/2"

 

9.0

 

1.1 / 1.7

3.7 / 4.0

1"+2"

 

2"

 

15.0

 

2.2 / 3.1

5.7 / 6.1

1"+2"

 

2-1/2"

 

24.0

 

2.7 / 4.0

6.5 / 7.0

1"+2"+3"

 

3"

 

36.0

 

4.3 / 6.2

10.7 / 11.4

1"+2"+3"

 

4"

 

60.0

 

11.4 / 14.7

27.7 / 29.0

70 mm

126 mm

65 mm

54 mm

135 mm

113 mm

PG11

R1”

1"+2"+3"+Z*

4" Z

60.0

6.1 / 8.0

17.3 / 18.4

1"+2"+3"

5"

94.0

22.9

/ 28.4

53.3 / 55.6

1"+2"+3"+Z*

5" Z

94.0

9.3 / 12.9

25.2 / 26.8

1"+2"+3"

6"

120.0

35.9 / 43.1

81.7 / 85.1

1"+2"+3"+Z*

6" Z

120.0

12.3 / 16.8

30.6 / 32.7

1"+2"+3

8"

240.0

72.6 / 85.1

165.7 / 172.5

1"+2"+3"+Z*

8" Z

240.0

38.6 / 46.5

90.8 / 94.2

*For models with the suffix “Z,” the longest paddle must be used to obtain the values indicated in this table. The Z = 8” paddle must be cut to the proper length to fit into the pipe without touching the inside.

1”

2”

3”

L

29 mm

 

Fig. 2. S6065A1003 dimensions

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

135 mm

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

70 mm

 

 

 

 

 

 

 

 

113 mm

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FIELD WIRING

COMMON

RED

NORMALLY OPEN

BLUE

NORMALLY CLOSED

WHITE

ADJUSTMENT SCREW

FOR FLOW RATE

Fig. 1. Field wiring

Connect the red and the white contacts. The contact red- white opens when the flow drops below the switch point.

 

 

 

 

 

 

72 mm

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

mm

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

132

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

54 mm

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1”

2”

3”

L

29 mm

52 mm

R1”

 

 

 

 

 

 

 

 

 

PG11

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

diameter

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4.5 mm

90 mm

When the flow is absent, the contact red-blue closes and can be used as a signal or alarm contact.

Fig. 3. S6065A2001 dimensions

Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl, Rolle, Z.A. La Pièce 16, Switzerland by its Authorized Representative:

Automation and Control Solutions

Honeywell GmbH

Böblinger Strasse 17 71101 Schönaich Germany

Phone: (49) 7031 63701

Fax: (49) 7031 637493 http://ecc.emea.honeywell.com

Subject to change without notice. Printed in Germany

EN0B-0314GE51 R1008

Image 2
Contents General FeaturesCommon Specifications MountingField Wiring SWITCH-POINT AdjustmentDimensions