Greenheck Fan 47555 specifications Receiving, Unpacking, Handling, Storage

Page 2

Receiving

Upon receiving the product, check to make sure all items are accounted for by referencing the bill of lading to ensure all items were received. Inspect each crate for shipping damage before accepting delivery. Notify the carrier if any damage is noticed. The carrier will make notification on the delivery receipt acknowledging any damage to the product. All damage should be noted on all the copies of the bill of lading which is countersigned by the delivering carrier. A Carrier Inspection Report should be filled out by the carrier upon arrival and the Traffic Department. If damaged upon arrival, file claim with carrier. Any physical damage to the unit after acceptance is not the responsibility of Greenheck Fan Corporation.

Unpacking

Verify that all required parts and the correct quantity of each item have been received, including accessory kit containing flex connector, gasketing, etc. If any items are missing report shortages to your local representative to arrange for obtaining missing parts. Sometimes it is not possible that all items

for the unit be shipped together due to availability of transportation and truck space. Confirmation of shipment(s) must be limited to only items on the bill of lading.

Handling

Fans are to be rigged and moved by the lifting brackets provided or by the skid when a forklift is used. Location of brackets varies by model and size. Handle each piece in such a manner as to keep from scratching or chipping the coating. Damaged finish may reduce ability of fan to resist corrosion. See coating repair section of this manual for details involving touch-up of damaged surfaces.

Fans should never be lifted by the shaft, fan housing, motor, belt guard, weatherhood, windband or other accessories.

Storage

Fans are protected against damage during shipment. If the unit cannot be installed and operated immediately, precautions need to be taken to prevent deterioration of the unit during storage. The user assumes responsibility of the fan and accessories while in storage. The manufacturer will not be responsible

for damage during storage. These suggestions are provided solely as a convenience to the user.

INDOOR

The ideal environment for the storage of fans and accessories is indoors, above grade, in a low humidity atmosphere which is sealed to prevent the entry of blowing dust, rain, or snow. Temperatures should

be evenly maintained between 30°F (-1°C) and 110°F (43°C) (wide temperature swings may cause condensation and “sweating” of metal parts). All accessories must be stored indoors in a clean, dry atmosphere.

Remove any accumulations of dirt, water, ice or snow and wipe dry before moving to indoor storage. To avoid “sweating” of metal parts allow cold parts to reach room temperature. To dry parts and packages use a portable electric heater to get rid of any moisture build up. Leave coverings loose to permit air circulation and to allow for periodic inspection.

The unit should be stored at least 3½ in. (89 mm) off the floor on wooden blocks covered with moisture proof paper or polyethylene sheathing. Aisles between parts and along all walls should be provided to permit air circulation and space for inspection.

OUTDOOR

Fans designed for outdoor applications may be stored outdoors, if absolutely necessary. Roads or aisles for portable cranes and hauling equipment are needed.

The fan should be placed on a level surface to prevent water from leaking into the fan. The fan should be elevated on an adequate number of wooden blocks so that it is above water and snow levels and has enough blocking to prevent it from settling into soft ground. Locate parts far enough apart to permit air circulation, sunlight, and space for periodic inspection. To minimize water accumulation, place all fan parts on blocking supports so that rain water will run off.

Do not cover parts with plastic film or tarps as these cause condensation of moisture from the air passing through heating and cooling cycles.

Fan wheels should be blocked to prevent spinning caused by strong winds.

Inspection and Maintenance during Storage

While in storage, inspect fans once per month. Keep a record of inspection and maintenance performed; see page 15.

If moisture or dirt accumulations are found on parts, the source should be located and eliminated. At each inspection, rotate the wheel by hand ten to fifteen revolutions to distribute lubricant on motor and bearings. If paint deterioration begins, consideration should be given to touch-up or repainting. Fans with special coatings may require special techniques for touch-up or repair.

Machined parts coated with rust preventive should be restored to good condition promptly if signs of rust occur. Immediately remove the original rust preventive coating with petroleum solvent and clean with lint-free cloths. Polish any remaining rust from surface with crocus cloth or fine emery paper and oil. Do not destroy the continuity of the surfaces. Wipe clean thoroughly with Tectyl® 506 (Ashland Inc.) or the equivalent. For hard to reach internal surfaces or for occasional use, consider using Tectyl® 511M Rust Preventive or WD-40®or the equivalent.

 Vektor-CD Centrifugal Laboratory Exhaust

®

Image 2
Contents Installation, Operation and Maintenance Manual General Safety InformationUnpacking Inspection and Maintenance during StorageReceiving HandlingRigging / Assembly Instructions InstallationStandard Fan Configurations System Identification TagsStructural Steel Curb InstallationsBases-Foundation and Isolation Concrete DeckLab Exhaust Riser Riser InstallationPlenum Assembly Plenum Isometric ViewPlenum Installation Modular Plenum Isometric ViewFan Installation Plenum and Fan Drainage Piping and Trap Detail by others Vektor Field Coating Repair Procedure for Scratched AreasDuct Connections to the Bypass Air Plenum BAP For Vektor Fans with a WeatherhoodApplications with Variable Frequency Drives VFD Motor Disconnect Wiring & Isolation Damper Wiring DiagramFor Vektor Fans without a Weatherhood Isolation Damper ControlVibration Unit Start-UpAdditional steps for initial start-up Fan Operation Serviceable ComponentsRoutine Maintenance & Operation Belt DrivesMotors ServiceBelt Drive Installation Belt Drive BearingsBearing Replacement Radial Gap, Overlap & Wheel AlignmentUnit Identification TroubleshootingProblem Cause Corrective Action Maintenance Log Warranty

47555 specifications

The Greenheck Fan model 47555 represents an innovative solution in air movement technology, designed for various applications requiring efficient and reliable ventilation. This powerful fan embodies advanced engineering and cutting-edge design to optimize airflow while maintaining energy efficiency.

One of the main features of the Greenheck 47555 is its robust construction. Built with high-grade materials, it withstands the rigors of commercial and industrial environments, ensuring longevity and durability. The fan is designed for easy installation and maintenance, which minimizes downtime and operational disruptions.

The 47555 utilizes an advanced airfoil blade design, which enhances performance by maximizing airflow and reducing noise levels. The aerodynamic shape of the blades is specifically engineered to move air efficiently, reducing power consumption while providing optimal ventilation. This characteristic aligns with the growing demand for environmentally friendly solutions in today’s market.

Equipped with a direct drive motor, the Greenheck 47555 offers increased reliability and reduced maintenance needs, as there are fewer moving parts that can wear out over time. The motor is designed to provide peak efficiency at various operating conditions, ensuring that energy usage is minimized without compromising performance.

The fan also includes adjustable speed options, allowing users to tailor airflow to specific requirements. This feature enhances control over ventilation and can contribute to energy savings, especially in applications where variable airflow is needed throughout the day.

Incorporating advanced technology, the Greenheck 47555 is capable of integrating with building management systems for remote monitoring and control. This connectivity enables operators to manage airflow and energy use proactively, aligning with modern smart building initiatives.

Additionally, the unit is available in various sizes and configurations, making it adaptable to a wide range of applications, from commercial kitchens to industrial warehouses. Customization options are also offered to meet unique project specifications.

In summary, the Greenheck Fan model 47555 is a powerful, reliable, and efficient choice for those looking to maintain optimal air quality in their spaces. With its advanced features, durable construction, and energy-efficient design, it meets the demands of modern ventilation needs while contributing to sustainability goals.