Greenheck Fan 47555 specifications For Vektor Fans without a Weatherhood, Isolation Damper Control

Page 9

For Vektor Fans without a Weatherhood

A guard / cover is located on the side of the plenum section. Removal of the guard / cover gains access to the damper linkages, actuator (optional from factory) and transformer (optional from factor). The entire bypass damper assembly can be removed through this opening. The isolation damper assembly can be removed from its location by unbolting the frame from the plenum and removing the flex connector.

If the Vektor units were not supplied with optional actuators, the dampers have an extended jackshaft for field mounting a customer supplied actuator.

Motor Disconnect Wiring & Isolation Damper Wiring Diagram

LINE IN

208/230/460/575 V

3 PHASE

DISCONNECT

208/230/460/575 V

3 PHASE

MOTOR 208/230/460/575/60/3

Disconnect is mounted to fan housing. Transformer is mounted to bypass air plenum near isolation damper actuator motor. For systems that ship un-assembled because of physical size, this connection at disconnect from transformer must be field installed. Wires with conduit and fitting are provided pre-connected to transformer.

OPTIONAL ISOLATION

DAMPER CONTROL

TRANSFORMER

208/230/460/575 V 1 PHASE

24/115 V 1 PHASE

ISOLATION DAMPER

ACTUATOR MOTOR

POWER OPEN/SPRING CLOSE

 

NOTE: If a Variable Frequency Drive is used to control fan speed,

FIELD WIRING

transformer and actuator will not function properly when wired as

FACTORY WIRING

shown. Transformers must be wired independently from VFD control.

Applications with Variable Frequency Drives (VFD)

For Vektor systems with single-point, three-phase wiring per blower, the isolation damper actuator will be powered via a step-down transformer, which is wired to the fan disconnect, as shown in the diagram above.

If fan flow (motor speed) is to be controlled using a VFD, the reduced voltage and frequency supplied to the fan will cause control problems with the isolation damper actuator.

When a Vektor control sequence requires the use of a VFD, it is suggested that the control contractor supply the isolation damper actuator voltage — independent of the power supplied to the Vektor fan motor.

Isolation Damper Control

Isolation dampers on de-energized fans are to be closed to maintain system negative pressure and prevent reverse “free-wheeling” of de-energized blower(s). Isolation dampers shall be opened immediately upon fan energizing.

®

Vektor-CD Centrifugal Laboratory Exhaust 

Image 9
Contents General Safety Information Installation, Operation and Maintenance ManualReceiving Inspection and Maintenance during StorageUnpacking HandlingStandard Fan Configurations InstallationRigging / Assembly Instructions System Identification TagsBases-Foundation and Isolation Curb InstallationsStructural Steel Concrete DeckPlenum Assembly Riser InstallationLab Exhaust Riser Plenum Isometric ViewModular Plenum Isometric View Plenum InstallationFan Installation Duct Connections to the Bypass Air Plenum BAP Vektor Field Coating Repair Procedure for Scratched AreasPlenum and Fan Drainage Piping and Trap Detail by others For Vektor Fans with a WeatherhoodFor Vektor Fans without a Weatherhood Motor Disconnect Wiring & Isolation Damper Wiring DiagramApplications with Variable Frequency Drives VFD Isolation Damper ControlUnit Start-Up Additional steps for initial start-upVibration Routine Maintenance & Operation Serviceable ComponentsFan Operation Belt DrivesBelt Drive Installation Belt Drive ServiceMotors BearingsRadial Gap, Overlap & Wheel Alignment Bearing ReplacementTroubleshooting Problem Cause Corrective ActionUnit Identification Maintenance Log Warranty

47555 specifications

The Greenheck Fan model 47555 represents an innovative solution in air movement technology, designed for various applications requiring efficient and reliable ventilation. This powerful fan embodies advanced engineering and cutting-edge design to optimize airflow while maintaining energy efficiency.

One of the main features of the Greenheck 47555 is its robust construction. Built with high-grade materials, it withstands the rigors of commercial and industrial environments, ensuring longevity and durability. The fan is designed for easy installation and maintenance, which minimizes downtime and operational disruptions.

The 47555 utilizes an advanced airfoil blade design, which enhances performance by maximizing airflow and reducing noise levels. The aerodynamic shape of the blades is specifically engineered to move air efficiently, reducing power consumption while providing optimal ventilation. This characteristic aligns with the growing demand for environmentally friendly solutions in today’s market.

Equipped with a direct drive motor, the Greenheck 47555 offers increased reliability and reduced maintenance needs, as there are fewer moving parts that can wear out over time. The motor is designed to provide peak efficiency at various operating conditions, ensuring that energy usage is minimized without compromising performance.

The fan also includes adjustable speed options, allowing users to tailor airflow to specific requirements. This feature enhances control over ventilation and can contribute to energy savings, especially in applications where variable airflow is needed throughout the day.

Incorporating advanced technology, the Greenheck 47555 is capable of integrating with building management systems for remote monitoring and control. This connectivity enables operators to manage airflow and energy use proactively, aligning with modern smart building initiatives.

Additionally, the unit is available in various sizes and configurations, making it adaptable to a wide range of applications, from commercial kitchens to industrial warehouses. Customization options are also offered to meet unique project specifications.

In summary, the Greenheck Fan model 47555 is a powerful, reliable, and efficient choice for those looking to maintain optimal air quality in their spaces. With its advanced features, durable construction, and energy-efficient design, it meets the demands of modern ventilation needs while contributing to sustainability goals.