Generac Power Systems 005221-0 Generator Control Operation, ‹ Engine START-UP and Transfer

Page 15

Standby Generator Sets

Operation

GENERATOR CONTROL AND

OPERATION

Refer to the appropriate control panel operator’s manual for this unit.

OPERATING UNIT WITH MANUAL TRANSFER SWITCH

If the generator was installed in conjunction with a transfer switch capable of manual operation only, the following procedure applies. A manually operated transfer switch is one that will not provide automatic start-up and does not include an intelligence circuit.

‹ENGINE START-UP AND TRANSFER

For additional information, refer to the applicable control panel manual for this unit, as well as any lit- erature pertaining to the specific transfer switch.

DANGER

The Maintenance Disconnect Switch and the AUTO/OFF/MANUAL switches (if so equipped) must be set properly, or the generator will crank and start as soon as the utility power to the transfer switch is turned off. Refer to applicable control panel and transfer switch manuals for more information.

Do not proceed until certain that utility source voltage is available to the transfer switch and the transfer switch main contacts are set to

UTILITY.

Do not attempt manual operation until all power supplies to the transfer switch have been posi- tively turned off, or extremely dangerous - pos- sibly lethal - electrical shock will result.

Transfer switch enclosure doors should be kept closed and locked. Only authorized personnel should be allowed access to the transfer switch interior. Extremely high and dangerous voltages are present in the transfer switch.

In order to transfer load from the utility source to the generator, follow these directions:

Turn OFF or disconnect the utility power circuit to the transfer switch, using the means provided (such as the utility source main line circuit break- er).

Set the transfer handle to its UTILITY (NORMAL) position with load circuits connected to the utility power supply.

Set the standby generator’s main line circuit break- er to its OFF (or OPEN) position.

Start the generator.

Do not crank the engine continuously for longer than 30 seconds, or the heat may

damage the starter motor.

Let engine stabilize and warm up.

Check all applicable instrument and gauge read- ings. When certain that all readings are correct, move the transfer switch manual handle to its STANDBY (GENERATOR) position, i.e., load cir- cuits supplied by the generator.

Set the standby generator’s main line circuit break- er to its ON (or CLOSED) position.

Load circuits are now powered by the standby generator.

‹RETRANSFER AND SHUTDOWN

For additional information, refer to the applicable control panel manual for this unit, as well as any lit- erature pertaining to the specific transfer switch.

To transfer the load back to the utility power source and shut down the generator, follow these direc- tions:

Set the standby generator’s main line circuit break- er to its OFF (or OPEN) position.

Manually move the transfer switch handle to its UTILITY (NORMAL) position, i.e., load circuits connected to the utility.

Turn ON the utility power supply to the transfer switch, using the means provided (such as the util- ity power source main line circuit breaker).

Let the generator run at no-load for a few minutes to stabilize internal temperatures.

Shut down the generator.

OPERATING UNIT WITH AUTOMATIC TRANSFER SWITCH

If the generator has been installed with an automatic transfer switch, such as an RTS, HTS, or GTS-type transfer switch, the engine may be started and stopped automatically or manually.

NOTE:

Refer to the applicable manual for your trans- fer switch and to “Transfer Switch Start Signal Connections”. In addition, please note the dangers under “Engine Start-up and Transfer.”

9-1

08/05

0 .Rev Oper001

Image 15
Contents Model Standby Generator Sets Table of Contents  Warning   Electrical Hazards  Introduction ‹ Operation and Maintenance‹ HOW to Obtain Service Authorized Service Dealer Location‹ Data Label Identification RecordEquipment Description Engine OIL RecommendationsCoolant Recommendations Engine Protective Devices ‹ LP Fuel System Fuel System‹ Fuel Requirements ‹ Natural GAS Fuel SystemSpecifications ‹ Cold Weather KIT ‹ Reconfiguring the Fuel SystemGenerator AC Lead Connections Alternator Power Winding Connections‹ FOUR-LEAD, SINGLE-PHASE Stator ‹ 3-PHASE AlternatorsInstallation Preparation Before START-UPInitial Inspection for QT Genset Startup START-UP Checklist ‹ Preparation for START-UP‹ START-UP Inspection ‹ Retransfer and Shutdown Operating Unit with Manual Transfer SwitchGenerator Control Operation ‹ Engine START-UP and TransferChecking Fluid Levels Cooling SystemMaintenance Owner Operator can Perform Miscellaneous Maintenance Repair Parts ‹ Battery Maintenance‹ Battery Replacement KW 150 KW Standby GAS Engine Driven Generator Sets Service ScheduleMaintenance Level 11-3 11-4 Problem Cause Correction Troubleshooting GuideStandby Generator Sets Page PAN CB Conn BOX Page Assy RTR 390 30KD1 CPL Page Components Included in 01827E Page MTG Base 3.9L 40KW C2 Page Tray Battery Page Flexplate HSB 3.9L Chrysler 1800RPM Page Weldment RAD Support 3.9L C2 Page Pipe R/H Side Muffler Page Element AIR Filter Page Page Page Flange Fuel Inlet Page Rear Wrap C2 Page Page Page Page Page Page Page Page Page Page Standby Generator Sets Warranty

005221-0 specifications

Generac Power Systems 005221-0 is a highly reliable portable generator that stands out in the market for its efficiency and advanced features. Designed for both home and recreational use, this generator delivers power when it's needed most, ensuring that users can stay connected and maintain their activities during power outages or job sites without electricity.

One of the main features of the Generac 005221-0 is its robust engine design. It is powered by a reliable OHV (Overhead Valve) engine that offers a consistent power output while maintaining fuel efficiency. This design ensures that the generator can run for extended periods, making it perfect for emergency situations or outdoor events.

The generator boasts a versatile power output, with a maximum capacity of 3,500 running watts and 4,500 starting watts. This level of output allows it to handle essential appliances like refrigerators, lights, and sump pumps, as well as power tools and other higher-demand equipment. The inclusion of multiple outlets, including both 120V and 30A twist-lock outlets, provides flexibility in power distribution, catering to different user needs.

One notable technology incorporated in the Generac 005221-0 is the PowerRush Technology, which offers an extra boost of power for starting larger appliances. This means that users can simultaneously power multiple devices without experiencing any performance dips. Furthermore, the generator is equipped with features that enhance user convenience, including an easy-to-read LED dashboard that displays key information such as power output and oil levels.

Durability and portability are other key characteristics of this generator. It features a compact and lightweight design combined with a sturdy frame and rubberized handle for easy transport. The never-flat wheels ensure that it can be moved easily across various terrains, making it suitable for job sites, camping trips, and other outdoor uses.

In terms of safety, the Generac 005221-0 is designed with an integrated circuit breaker to prevent overloads, as well as a low-oil shutdown feature that stops the engine when oil levels are critically low. This ensures that the generator operates safely and extends its lifespan.

Overall, the Generac Power Systems 005221-0 is an excellent choice for those in need of a dependable, efficient, and versatile portable generator. Its combination of innovative technology, robust features, and user-friendly design makes it a valuable asset for any home or outdoor enthusiast.