Honeywell 5820XL manual Addressing Hochiki Devices, 1 SD505-APS, SD505-AHS, & SD505-AIS

Models: 5820XL

1 228
Download 228 pages 29.8 Kb
Page 95
Image 95

Hochiki and SK SLC Device Installation

5.8Addressing Hochiki Devices

This section tells how to address detectors and modules.

5.8.1SD505-APS, SD505-AHS, & SD505-AIS

The SD505-APS photoelectric smoke detector, SD505-AHS heat detector, and SD505-AIS ionization smoke detector are easily addressed at the FACP. The Installer Code is required to perform this task.

To address a SD505-APS, SD505-AHS, or SD505-AIS:

1.Connect a detector base temporarily to the programming terminals as shown in Figure 5-7. (You can use the same base for each detector.)

Figure 5-7 Temporary Connection of Detector Base to Panel for Addressing

2.Enter the Installer code, then press ENTER .

3.Select 2 for Point Functions.

4.Select 3 for Set SLC Dev Addr.

5.Select “Yes” by pressing the up arrow, then press

ENTER . (The panel will go into

trouble at this point. You can use the SILENCE key to stop the PZT. The trouble will clear automatically when the panel re initializes when you finish programming.)

6. When the wait message clears, the following options display:

1

2

3

for Read Address. Use to read (or check) a single detector’s address.

for Write Address. Use to program a single detector’s address.

for Seq. Programming. Use to program more than one detector in sequential order.

7.If you are changing addresses, write the programmed address on the back of the device.

8.To exit press left arrow until fully exited.

151209

5-9

Page 95
Image 95
Honeywell 5820XL manual Addressing Hochiki Devices, 1 SD505-APS, SD505-AHS, & SD505-AIS