Control Panel Installation
4.15 Remote Station Applications
4.15.1 Keltron Model 3158 Installation
The control panel is compatible with Keltron Model 3158, used for direct connection to a Keltron receiver. The 3158 reports alarms, supervisories, and troubles.
The steps for connecting the 3158 to the control panel. Refer to the 3158 installation instructions for complete information.
1.Wire the 3158 to the control panel as shown in the connection list and Figure
2.Wire the 3158 within 20 feet of the control panel. Wiring must be enclosed in conduit.
3.Program control panel Relay 1 for alarm.
4.Program Flexput circuit 5 for alarm.
5.Program Flexput circuit 6 for supervisory non latching.
Table 4-3: Keltron 3158 to Control Panel Connections
Terminal # | Connects To |
|
|
|
|
3158 Term. 1 | To Keltron receiving equipment |
|
|
3158 Term. 2 | To Keltron receiving equipment |
|
|
3158 Term. 3 | Earth ground |
|
|
3158 Term. 4 | Not used; no connection. |
|
|
3158 Term. 5 | Control panel Term. 18 |
|
|
3158 Term. 6 | Control panel Term. 19 |
|
|
3158 Term. 7 | Control panel Term. 7 |
|
|
Not suitable for remote station protected premise service where separate transmission circuits are required for fire supervisory (if applicable), and trouble signals.
Intended for connection to a polarity reversal circuit of a remote station receiving unit having compatible ratings.
| Terminal # | Connects To |
|
|
|
|
|
|
3158 | Term. 8 | Control panel Term. 28 |
|
|
|
3158 | Term. 9 | Control panel Term. 5 |
|
|
|
3158 | Term. 10 | Control panel Term. 4 |
|
| |
Control panel Term. 6 | Control panel Term. 29 | |
|
| |
Control panel Term. 28 | Control panel Term. 31 | |
|
| |
Control panel Term. 29 | Control panel Term. 30 | |
|
|
|
Example
Figure 4-40 Keltron 3158 Connection to Control Panel
151209 |