System Operation
8.5.9Silence alarms or troubles
Press SILENCE and enter your code or rotate the key at the prompt. If an external silence switch has been installed, activating the switch will silence alarms or troubles. If you are
already using system menus when you press rotate the key.
SILENCE
, you will not need to enter your code or
Note: Alarm and trouble signals that have been silenced but the detector remains
8.5.10 Reset alarms
Press RESET and enter your code or rotate the key at the prompt. If an external reset switch has been installed, activating the switch will reset alarms. If you are already using system
menus when you press
RESET
, you will not need to enter your code or rotate the key.
8.5.11 Check Detector Through Point Status
The control panel constantly monitors smoke detectors to ensure that sensitivity levels are in compliance with NFPA 72.
If sensitivity for a detector is not in compliance, the panel goes into trouble, generating a CAL TRBLE condition. A detector enters a CAL MAINT state to indicate that it is approaching an out of compliance condition (but is currently still in compliance).
When a CAL TRBLE condition occurs, the central station receives a detector trouble report (“373” + Zone # for Contact ID format; “FT” + Zone # in SIA format).
To check sensitivity for an individual detector, follow the steps below. Section 8.5.17 provides instructions for printing the status of all detectors in the system.
1.From the Main Menu, press
2.Press 2 for Point Status.
2
for Point Functions.
3. Select the module where the point you want to check is located.
4. Enter the number of the point you want to check and press
ENTER .