Control Panel Installation

4.13.3 Installing 2-Wire Smoke Detectors

Any compatible U.L. listed two-wire smoke detector can be used with the control panel (see Appendix A for list of compatible smoke detectors). Figure 4-34and Figure 4-35illustrate how to connect a UL listed 2-wire detector to the control panel.

4.13.3.1 Installing 2-Wire Class B Smoke Detectors

To install a Class B two-wire smoke detector, wire as shown in Figure 4-34.

UL Listed EOL

Model 7628

4.7 kΩ

Supervised

Power Limited

Note:

Flexput circuit 5 used as an example. Any Flexput circuit could be used.

Figure 4-34 Two-Wire Class B Smoke Detector

151209

4-35