Honeywell 5820XL manual Installing 4-Wire Class a Smoke Detectors

Models: 5820XL

1 228
Download 228 pages 29.8 Kb
Page 76
Image 76

IntelliKnight 5820XL Installation Manual

4.13.4.2 Installing 4-Wire Class A Smoke Detectors

Figure 4-37illustrates how to install 4-wire Class A detectors.

Conventions used for wiring 4-wire Class A loops:

1.Up to two Class A 4-wire loops can be connected to the control panel at once.

2.Smoke power is supplied to each Class A loop as shown in Figure 4-37.

Air Products

PAM-2

Model 160150

Supervision

Module

Supervised Power Limited

Air Products

PAM-2

Model 160150

Supervision

Module

Figure 4-37 Class A 4-Wire Smoke Detector Connections

Note: In programming any point that uses multiple Flexput circuits are always referred to as the lowest Flexput circuit number used. For example, Figure 4-37uses Flexput circuits 1, 2, 3 together and 4, 5, 6 together. In programming (1, 2, 3) would be referred to as point 1, and (4, 5, 6) would be referred to as point 4.

4-38