Before You Begin Installing

3.6.2Current Draw Worksheet for SK SLC Devices

Use Table 3-1to determine current requirements during alarm/battery standby operation when SK SLC devices are installed. You can install up 99 SK detectors per loop (396 max per panel) and 99 SK modules per loop (396 max per panel). Copy this section if additional space is required.

Table 3-1: Current Draw Worksheet for SK SLC Devices

Device

# of Devices

 

Current per Device

Standby

Alarm

 

Current

Current

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

For each device use this formula:

This column

X This column

= Current per number of devices.

Fire Panel (Current draw from

1

 

Standby:

 

215 mA

215 mA

 

battery)

 

Alarm:

 

385 mA

 

385 mA

 

 

 

 

Addressable SLC Detectors

 

 

 

 

 

 

 

SK-Photo

 

 

 

 

 

mA

mA

SK-Photo-T

 

 

 

 

 

mA

mA

 

 

 

Standby/Alarm:

0.27 mA

 

 

SK-Ion

 

 

mA

mA

SK-Heat

 

 

 

 

 

mA

mA

SK-Heat-HT

 

 

 

 

 

mA

mA

 

 

 

SLC

Standby/

 

 

 

 

 

 

Alarm:

2 mA

 

 

SK-Beam (without integral test)

 

 

 

 

 

(99 max/loop

 

 

 

 

 

 

 

Aux. Pwr

Standby:

2 mA

mA

 

 

 

 

 

& 396 max/

 

Alarm:

8.5 mA

 

mA

 

panel)1

 

 

 

 

 

 

 

 

SLC

Standby/

 

 

 

 

 

 

Alarm:

2 mA

 

 

SK-Beam-T 5(with integral test)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Aux. Pwr

Standby:

2 mA

mA

 

 

 

 

 

 

 

 

Alarm:

8.5 mA

 

mA

SK-Duct6

 

 

SLC

Standby/

 

mA

mA

 

 

Alarm:

0.27 mA

 

 

 

 

 

 

SK-Acclimate

 

 

Standby/Alarm:

0.3 mA

mA

mA

SK-Heat-ROR

 

 

mA

mA

 

 

 

 

 

151209

3-7