System Operation
8.7.1Single Interlock Zone Releasing
A single interlock zone utilizes a minimum of two addressable detectors and a designated manual release switch.
Important!
Only addressable detectors can be used. No conventional detectors can be used.
Each Single Interlock Zone input requires at least one manual release switch.
Conditions Required for an Pre-Alert Output Activation
If any single addressable detector is activated, the
Conditions required for an General Alarm and Release Output Activation
If two or more addressable detectors, or a manual release switch activate, the “Alarm” and the “Release” outputs will activate. (Also refer to Table
Table 8-3: Single Interlock Zone Operation
Inputs |
|
|
| Output Results |
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1st Addressable Detector |
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
2nd Addressable Detector |
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
Manual Release Station |
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
| Normal | and General Alarm | and General Alarm | and General Alarm | and General Alarm | and General Alarm | ||
|
|
|
| Release | Release | Release | Release | Release |
|
|
|
|
|
|
|
|
|