IntelliKnight 5820XL Installation Manual

7.7.4Miscellaneous Options 1

Through this programming option you can set the water flow delay time, low AC report delay, enable or disable automatic daylight savings time adjustment, clock format, and AC clock frequency.

7.7.4.1 Water Flow Delay

You can program a delay of 0-90 seconds (zero means no delay) to be used in conjunction with a water flow switch. The delay is system-wide. All water flow switches on the system will use the same delay period.

To access the screen for programming water flow delay, follow these steps:

1.Enter the installer code.

2.Press or to display the main menu.

3.Select 7 for Program Menu.

Display reads:

Initializing

 

Please wait . . .

4.Select 5 for System Options.

5.Select 5 for Miscellaneous Options 1.

A screen similar to the one shown in Figure 7-16will display.

Delay in seconds before waterflow alarm occurs.

(00 - 90)

Figure 7-16 Water Flow Delay Programming Screen