IntelliKnight 5820XL Installation Manual
A.2 Two-Wire Smoke Detectors
Table
Table
| 5820XL |
|
|
Identifier | 24H |
|
|
Operating Voltage Range | |
|
|
Note: The maximum number of smoke detectors per zone is determined by both the current draw and the imped- ance of the smoke detector. If too many smoke detectors are used on any zone, false alarms could occur.
Do not mix different models of detectors on any zone; false alarms could occur.
Do not mix detectors of different models unless the system is specifically intended to be installed in that configuration.
Control unit Smoke Reset Time must be programmed for a number greater than or equal to the maximum reset time of the smoke detector.
Table A-2: Compatible Two-Wire Smoke Detectors
Manufacturer | Model Name or Number | Compatibility ID | # per Loop | ||
(Base model name or number |
|
| |||
Head | Base | ||||
| in parentheses.) |
| |||
|
|
|
|
| |
|
|
|
|
| |
Apollo | 24 / loop | ||||
|
|
|
| ||
24 / loop | |||||
| |||||
|
|
|
|
| |
Apollo | 15 / loop for | ||||
|
|
|
| Ion Detectors | |
|
| ||||
|
|
| |||
|
|
|
|
| |
|
| 15 / loop for | |||
|
|
| |||
| |||||
| Photo Electric | ||||
| 230, 232, 251,252 | ||||
|
|
| |||
| Detectors | ||||
|
| ||||
|
|
|
|
| |
|
|
| |||
|
|
|
|
| |
|
|
| |||
|
|
|
|
|
151209 |