IntelliKnight 5820XL Installation Manual
8.5.7Conduct a Walk Test
1. From the Main Menu, press
1
for System Tests.
IMPORTANT!
If any alarm verification zones are being used, the user will be asked if they wish to disable alarm verification during walk test. This occurs for either walk test option.
2.Select 3 for Walk
Or
Select 4 for Walk
The panel generates a TEST report to the central station when the walk test begins. During a walk test, the panel’s normal fire alarm function is completely disabled, placing the panel in a local trouble condition. All zones respond as
3.Press ENTER to end the walk test. The system will reset. The panel will send a "TEST RESTORE" report to the central station.
If you do not end the walk test manually within four hours, it will end automatically.
If an alarm or
Note: the panel does not do a full 30 second reset on resettable power outputs. As soon as the device is back to normal, the panel is ready to go to the next device.
8.5.8Conduct a Dialer Test
1. From the Main Menu, press
1
for System Tests.
2.Select 5 for Dialer Test. The screen will display “Manual dialer test started”. When the test is completed, you will be returned to the <Test Menu>.