IntelliKnight 5820XL Installation Manual
3.6.4Maximum Battery Standby Load
Table
* 33AH max battery size for FM (Factory Mutual) installations..
Table 3-3: Maximum Battery Standby Load
Rechargeable Battery Size | Max. Load for 24 hrs. | *Max. Load for 60 hrs. | |
Standby, 5 mins. Alarm | Standby, 5 mins. Alarm | ||
| |||
|
|
| |
|
|
| |
7 AH | 270 mA | 105 mA | |
12 AH | 475 mA | 190 mA | |
|
|
| |
18 AH | 685 mA | 270 mA | |
|
|
| |
35 AH | 1.3 A | 540 mA | |
|
|
|
*Required for NFPA 72 Auxiliary Protected Fire Alarm systems for Fire Alarm Service (City Box) and Remote Station Protected Fire Alarm systems (Polarity Reversal) and Digital Alarm Communicator/Transmitter (DACT).
Warning!
Silent Knight does not support the use of batteries smaller than those listed in Table
3.7Installation Tasks Overview
This section provides a chart listing tasks that need to be performed when installing the IntelliKnight 5820XL system. The chart is intended to be a handy way for you to make sure you have completed all necessary tasks. Unless noted, these tasks do not have to be performed in the order they are listed here.
Important: Connect and address SLC devices before running JumpStart.
Task | See Sec. | |
(for more info.) | ||
| ||
|
| |
|
| |
Main Panel Hardware Installation |
| |
|
|
Mount the control panel cabinet. | 4.1 |
|
|
Connect AC. | 4.2 |
|
|
Connect phone lines. | 4.11 |
|
|
Install 5815XL SLC expander modules (if needed). Required if more than | 4.6 |
127 SLC devices are used. |
|
|
|
Install 5860 Remote Fire Alarm Annunciator modules if used. | 4.5 |
|
|
Install 5865 or LED Annunciator modules if used. | 4.9 |
|
|
Install 5880 LED I/O module if customized LED annunciation will be used. | 4.8 |
|
|
Install notification appliances. | 4.13 |
|
|
Install auxiliary power devices (if used). | 4.13.5 |
|
|
If using a printer, install the 5824 Serial/Parallel Printer Interface Module. | 4.7 |
|
|
Connect batteries (typically last step). | 4.3 |