Honeywell 5820XL manual Auxiliary Power Installation, Door Holder Power, Constant Power

Models: 5820XL

1 228
Download 228 pages 29.8 Kb
Page 77
Image 77

Control Panel Installation

4.13.5 Auxiliary Power Installation

Flexput Circuits 1-6 on the control panel can be used as auxiliary power circuits. The three types of auxiliary power available are:

Door Holder (see Section 4.13.5.1)

Constant (see Section 4.13.5.2)

Resettable Power (see Section 4.13.5.3)

Auxiliary power circuits are power limited. Each circuit can source up to 3A (total current for all Flexput circuits must not exceed 6.0 A).

To install an auxiliary power circuit:

1.Wire the Flexput circuit(s) that will be used for auxiliary power. See Figure 4-38for loca- tion of Flexput circuits.

2.Configure the auxiliary power output through programming (see Section 7.6).

Figure 4-38 Flexput Circuit Location

4.13.5.1 Door Holder Power

Door holder power is intended for fire door applications. When there are no alarms in the system and the panel has AC power, door holder circuits have 24-volt power present at their terminals. Any alarm will cause power to disconnect. Power will be re-applied when the system is reset. If AC power is off for more than 15 seconds, the auxiliary door holder power will be disconnected to conserve the battery backup. When AC power is restored, power is immediately restored to the door holder circuits.

Use a UL listed door holder ESL DHX-1224, for this application.

4.13.5.2 Constant Power

Use constant power for applications that require a constant auxiliary power source. Power is always present at Constant circuits.

151209

4-39

Page 77
Image 77
Honeywell 5820XL manual Auxiliary Power Installation, Door Holder Power, Constant Power