Control Panel Installation
4.13.5 Auxiliary Power Installation
Flexput Circuits
•Door Holder (see Section 4.13.5.1)
•Constant (see Section 4.13.5.2)
•Resettable Power (see Section 4.13.5.3)
Auxiliary power circuits are power limited. Each circuit can source up to 3A (total current for all Flexput circuits must not exceed 6.0 A).
To install an auxiliary power circuit:
1.Wire the Flexput circuit(s) that will be used for auxiliary power. See Figure
2.Configure the auxiliary power output through programming (see Section 7.6).
Figure 4-38 Flexput Circuit Location
4.13.5.1 Door Holder Power
Door holder power is intended for fire door applications. When there are no alarms in the system and the panel has AC power, door holder circuits have
Use a UL listed door holder ESL
4.13.5.2 Constant Power
Use constant power for applications that require a constant auxiliary power source. Power is always present at Constant circuits.