Honeywell 5820XL Receivers Compatible with the Control Panel, Reporting Formats Dialer Outputs

Models: 5820XL

1 228
Download 228 pages 29.8 Kb
Page 183
Image 183

Section 9

Reporting

This section lists receivers that are compatible with this control panel, and the reporting codes sent by the control panel for SIA and Contact ID formats.

9.1Receivers Compatible with the Control Panel

Table 9-1 shows receivers compatible with the control panel.

Table 9-1: Receivers Compatible with the Control Panel

Manufacturer

Model

Format

 

 

 

 

 

 

Silent Knight

Model 9800

SIA and Contact ID

 

 

Model 9000 (SIA formats)

SIA

 

 

 

 

Ademco

Model 685 (Contact ID )

Contact ID

 

 

 

Sur-Gard

SG-MLR2-DG (V. 1.64 or higher)

SIA and Contact ID

 

 

 

Osborne Hoffman

Quickalert

SIA and Contact ID

 

 

 

9.2Reporting Formats Dialer Outputs

 

 

 

SIA Reporting Format

Contact ID Reporting Format

 

 

 

 

 

 

 

 

 

 

 

Event

Event Class

Module

SIA

Parameter

 

Event

Group

Contact

Event Description

(System, Zone,

ID #

Event

Qualifier

Family

(if any)

Code

#

#

 

or Point)

(if any)

Code

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

System Events

Note:

Note: System events are reported when either "Report by Point" or "Report by

Zone" is selected.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AC power restore

Trouble

System Event

 

AR

 

3

301

00

000

 

 

 

 

 

 

 

 

 

 

AC power lost

Trouble

System Event

 

AT

 

1

301

00

000

 

 

 

 

 

 

 

 

 

 

SBUS expander trouble restore

Trouble

System Event

 

ER

Exp. ID

3

333

00

Exp. ID

 

 

 

 

 

 

 

 

 

 

SBUS Class A supervision restore

Trouble

System Event

 

ER

Exp. ID

3

333

00

Exp. ID

 

 

 

 

 

 

 

 

 

 

Short circuit removed from SLC

Trouble

System Event

 

ER

Exp. ID

3

332

00

Exp. ID

communication loop

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SLC Class A supervision restored

Trouble

System Event

 

ER

Exp. ID

3

331

00

Exp. ID

 

 

 

 

 

 

 

 

 

 

SBUS expander trouble

Trouble

System Event

 

ET

Exp. ID

1

333

00

Exp. ID

 

 

 

 

 

 

 

 

 

 

SBUS Class A supervision lost

Trouble

System Event

 

ET

Exp. ID

1

333

00

Exp. ID

 

 

 

 

 

 

 

 

 

 

Short circuit detected on SLC com-

Trouble

System Event

 

ET

Exp. ID

1

332

00

Exp. ID

munication loop

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SLC Class A supervision lost

Trouble

System Event

 

ET

Exp. ID

1

331

00

Exp. ID

 

 

 

 

 

 

 

 

 

 

Fire drill has begun

Test

System Event

 

FI

 

1

604

00

000

 

 

 

 

 

 

 

 

 

 

Fire drill ended

Test

System Event

 

FK

 

3

604

00

000

 

 

 

 

 

 

 

 

 

 

Panel date has been changed

Trouble

System Event

 

JD

 

1

625

00

000

 

 

 

 

 

 

 

 

 

 

151209

9-1

Page 183
Image 183
Honeywell 5820XL Receivers Compatible with the Control Panel, Reporting Formats Dialer Outputs, Manufacturer Model Format