Control Panel Installation
4.15.3 NFPA 72 Polarity Reversal
Note: Intended for connection to a polarity reversal circuit of a control unit at the protected premises having compatible rating.
4.15.3.1 Using the 5220 Module
When the 5220 is wired and programmed for polarity reversal, it reports alarm and trouble events to a remote site. Alarms will override trouble conditions and it will not be possible to reset the remote indicator until the condition is cleared and the control panel is reset.
If an alarm condition occurs, the alarm relay will close, overriding the trouble condition.
Standby Current: | 100 mA, 24 VDC |
Alarm: | 100 mA, 24 VDC |
To install the 5220 for polarity reversal, follow the steps below:
1.Locate the knockout on the right side of the control panel cabinet to connect the 5220 using a short piece of conduit (must not exceed 20 feet in length).
2.Wire the 5220 to the control panel using the
3.Connect earth ground wire to the 5220 chassis with mounting screw.
4.Program the Flexput circuit used as a notification circuit, continuous and
5.If necessary, adjust loop current using the potentiometer (R10) on the 5220 board . Normal loop current is
Note:
Flexput circuit 1 and Relay 1 used as examples. Any Flexput circuit and either relay 1 or relay 2 could
be used.
All circuits
All wiring supervised.
Intended for connection to a Polarity Reversal | Jumper these terminals |
circuit of a Remote Station receiving unit having | when City Box is not used. |
compatible ratings. |
|
Figure 4-42 Polarity Reversal Connection Using the 5220 Module