Wiring Distance calculation example:
Suppose a system is configured with the following SBUS modules: 2 - Module 5860 Fire Annunciator
1 - 5895XL Intelligent Power Expander
1 - 5865 LED Fire Annunciator
1 - 5824 Serial/Parallel Interface Module
The total worst case current is calculated as follows:
5860 Current Draw | = 2 x .100 amps | = .200 amps |
5895XL Current Draw | = 1 x .010 amps | = .010 amps |
5865 Current Draw | = 1 x .200 amps | = .200 amps |
5824 Current Draw | = 1 x .040 amps | = .040 amps |
|
|
|
Total Worst Case Current Draw |
| = .450 amps |
Using this value, and referring to the Wiring Distance table, it can be found that the available options are:
370 feet maximum using 22 Gauge wire
938 feet maximum using 18 Gauge wire
1493 feet maximum using 16 Gauge wire
2362 feet maximum using 14 Gauge wire