Control Panel Installation
These cases are marked in the chart with an asterisk (*). Maximum length can never be more than 6,000 feet, regardless of gauge used. (The formula used to generate this chart is shown in the note below).
Table 4-1: Wire Distances Per Wire Gauge Using Copper Wire
Wiring Distance: SBUS Modules to Panel
Total Worst Case | 22 Gauge | 18 Gauge | 16 Gauge | 14 Gauge | |
Current Draw (amps) | |||||
|
|
|
| ||
|
|
|
|
| |
|
|
|
|
| |
0.100 | 1852 ft. | 4688 ft. | * 6000 ft. | * 6000 ft. | |
|
|
|
|
| |
0.200 | 926 ft. | 2344 ft. | 3731 ft. | 5906 ft. | |
|
|
|
|
| |
0.300 | 617 ft. | 1563 ft. | 2488 ft. | 3937 ft. | |
|
|
|
|
| |
0.400 | 463 ft. | 1172 ft. | 1866 ft. | 2953 ft. | |
|
|
|
|
| |
0.500 | 370 ft. | 938 ft. | 1493 ft. | 2362 ft. | |
|
|
|
|
| |
0.600 | 309 ft. | 781 ft. | 1244 ft. | 1969 ft. | |
|
|
|
|
| |
0.700 | 265 ft. | 670 ft. | 1066 ft. | 1687 ft. | |
|
|
|
|
| |
0.800 | 231 ft. | 586 ft. | 933 ft. | 1476 ft. | |
|
|
|
|
| |
0.900 | 206 ft. | 521 ft. | 829 ft. | 1312 ft. | |
|
|
|
|
| |
1.000 (Max) | 185 ft. | 469 ft. | 746 ft. | 1181 ft. | |
|
|
|
|
|
Note: The following formulas were used to generate the wire distance chart:
Maximum Resistance (Ohms) = | 6.0 Volts | ||
|
| ||
Total Worst Case Current Draw (amps) | |||
| |||
Maximum Wire Length (Feet) = | Maximum Resistance (Ohms) | ||
(6000 feet maximum) |
| * 500 | |
Rpu |
where: Rpu = Ohms per 1000 feet for various wire gauges (see table below)
Table 4-2: Typical Wire Resistance Per 1000 ft. Using Copper Wire
Wire Gauge | Ohms per 1000 feet (Rpu) |
|
|
|
|
22 | 16.2 |
|
|
18 | 6.4 |
|
|
16 | 4.02 |
|
|
14 | 2.54 |
|
|