3.6.3Current Draw Worksheet for Hochiki SLC Devices

Use Table 3-2to determine current requirements during alarm/battery standby operation when Hochiki SLC devices are installed. You can install up 127 Hochiki devices per loop (508 max per panel). Copy this section if additional space is required.

Table 3-2: Current Draw Worksheet for Hochiki SLC Devices

Device

 

# of Devices

Current per Device

Standby

Alarm

 

Current

Current

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

For each device use this formula:

This column X

This column

= Current per number of devices.

IntelliKnight 5820XL Fire Panel

 

1

Standby:

 

215 mA

215 mA

 

(Current draw from battery)

 

Alarm:

 

385 mA

 

385 mA

 

 

 

 

Addressable SLC Devices

 

 

 

 

 

 

 

SD500-AIM

 

 

 

 

 

mA

mA

SD500-MIM

 

 

 

 

 

mA

mA

SD500-PS

 

(508 max.)1

 

 

 

 

 

 

 

Standby/Alarm:

0.55 mA

 

 

SD500-ARM

 

mA

mA

SD505-AHS

 

 

 

 

 

mA

mA

SD505-AIS

 

 

 

 

 

mA

mA

SD505-APS

 

 

 

 

 

mA

mA

 

 

 

Aux. Pwr

Standby:

8 mA

mA

 

SD500-ANM

 

(508 max.)1

Alarm:

60 mA

 

mA

 

SLC

Standby/

 

mA

mA

 

 

 

Alarm:

.55 mA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SLC

Standby/

 

mA

mA

 

 

(508 max.)1

Alarm:

.55 mA

SD500-SDM

 

 

 

 

 

Aux. Pwr

Standby:

20 mA

mA

 

 

 

 

 

 

 

 

Alarm:

106 mA

 

mA

 

 

 

 

Standby:

10 mA

mA

 

SD500-LED

 

(100 max.)1

Aux. Pwr

Alarm:

220 mA

 

mA

 

 

LED:

10 mA

mA

mA

 

 

 

SLC

Standby/

 

mA

mA

 

 

 

Alarm:

0.55 mA

 

 

 

 

 

 

SLC Accessory Bases

 

 

 

 

 

 

 

SD505-6RB

 

(508 max.)

Standby/Alram:

.082 mA

mA

mA

 

 

 

Aux. Pwr

Standby:

1 mA

mA

 

SD505-6SB

 

(508 max.)

Alarm:

32 mA

 

mA

 

 

 

SLC

Standby/

 

mA

mA

 

 

 

Alarm:

.082 mA

 

 

 

 

 

 

 

 

 

 

Standby:

2

mA

 

SD505-ADHR

 

 

Aux. Pwr

35 mA

 

 

 

(508 max.)

Alarm:

75 mA2

 

mA

 

 

 

SD505-DUCTR

 

 

SLC

Standby/

 

mA

mA

 

 

 

Alarm:

.082 mA

 

 

 

 

 

 

 

 

 

 

 

 

 

SD505-DTS

 

(508 max.)

 

None, included with

SD505-ADHR worst case.

SD505-DTS-K

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SD505-ADH

 

(508 max.)

 

None, included with detector current.

 

SD505-DUCT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SLC Isolator Devices

 

 

 

 

 

 

 

SD500-LIM

 

(1024 max.)

Standby/Alarm

0.092 mA

mA

mA

SD505-6IB

 

(508 max.)

 

 

 

 

 

 

Accessories Modules

 

 

 

 

 

 

 

5815XL SLC Expander

 

(3 max.)

Standby/Alarm:

55 mA

mA

mA

5860 Remote Fire Alarm Annun.

 

(8 max.)

Standby:

 

20 mA

mA

 

 

Alarm:

 

25 mA

 

mA

 

 

 

 

 

3-10