![](/images/new-backgrounds/1041751/41751245x1.webp)
Programming
Alarm Delay Characteristics
3. Select the alarm delay characteristics (see Table or
arrow.
| Table | |
|
| |
Type of Delay | Description | |
|
| |
|
| |
| One Count (No Delay). When this option is enabled, an alarm occurs immediately when a single device | |
of any of the following types goes into alarm: detector, manual pull, water flow, Aux1 or Aux2. This is | ||
| considered the most typical operation and is the default for all zones. | |
|
| |
| When this type of alarm delay is used, two or more detectors within the zone must go into alarm in order | |
| for the zone to report an alarm. Switches of type manual pull, water flow, Aux1 and Aux2 are an | |
| exception; they will cause an alarm when only one switch is in alarm. | |
When a single detector is in alarm in a | ||
| prealarm condition, the touchpad PZT beeps and the annunciator display indicates that a prealarm has | |
| occurred. If the zone has been mapped to an output group for the prealarm event, the output group will | |
| activate. The prealarm will not be reported to the central station. | |
|
| |
| Alarm verification is an optional false alarm prevention feature that verifies an alarm condition by | |
Alarm Ver. | resetting the smoke detector. If the alarm condition still exists by the time the reset cycle has completed, | |
the detector will go into alarm. If the detector is no longer in alarm, no report will go to the central | ||
| ||
| station. The alarm verification sequence is ignored if the zone is already in alarm. | |
|
| |
| This option is intended to be used with an acknowledge switch. An alarm is delayed for 15 seconds, | |
| giving | |
| within 15 seconds, an alarm occurs automatically. | |
| If this option is enabled for a zone, the zone will respond to an alarm condition as follows: | |
| • The zone will not go into alarm for 15 seconds to allow an | |
| edge switch. | |
PAS | • If the operator does not press the acknowledge switch within 15 seconds, the zone will go into | |
| alarm. | |
| • If the operator presses the acknowledge switch within 15 seconds, a | |
| begin counting down. This | |
| If the operator performs a reset within 180 seconds, the alarm will not occur. If the operator does | |
| not perform a reset within 180 seconds, an alarm will occur automatically. | |
| • The P.A.S. feature will be overridden if another alarm occurs. | |
|
| |
SNGL ILOCK | See Section 8.7.1 for single interlock releasing operation. | |
|
| |
DBL ILOCK | See Section 8.7.2 for double interlock releasing operation. | |
|
| |
4. Press | . |
Heat Temperature Setting
Use this feature to set the temperature at which heat detectors will respond. The range is 135° to 150° F. All detectors in the zone will respond in the same way.
The Model
5.Enter the temperature at which the heat detector will respond. Or
Use the or
keys to scroll through the range or enter directly from the number keys
on the annunciator, then press .
6.Use the or
keys to scroll through the range or enter directly from the number keys on the annunciator.
151209 |