Control Panel Installation
4.13.2 Conventional Input Switch Circuits
This section of the manual explains how to install conventional initiating devices for Class A (Style D) or Class B (Style B) configurations.
4.13.2.1 Class B Inputs
You can connect conventional Class B switches, such as waterflow switches and pull stations, directly to the Flexput circuits of the control panel.
To install a Class B switch:
1.Wire the Class B switch as shown in Figure
2.Configure the circuit through programming (see Section 7.6).
Supervised
Power Limited
UL Listed EOL
Model 7628
4.7 kΩ
Figure 4-32 Class B Input Switches
151209 |