4.13.2 Conventional Input Switch Circuits

This section of the manual explains how to install conventional initiating devices for Class A (Style D) or Class B (Style B) configurations.

4.13.2.1 Class B Inputs

You can connect conventional Class B switches, such as waterflow switches and pull stations, directly to the Flexput circuits of the control panel.

To install a Class B switch:

1.Wire the Class B switch as shown in Figure 4-32.

2.Configure the circuit through programming (see Section 7.6).

Supervised

Power Limited

UL Listed EOL

Model 7628

4.7 kΩ

Figure 4-32 Class B Input Switches

151209

4-33