Honeywell 5820XL manual Section Programming, UL 864 Programming Requirements

Models: 5820XL

1 228
Download 228 pages 29.8 Kb
Page 117
Image 117

Section 7

Programming

This section of the manual describes how to manually program the control panel from the built-in annunciator. Each subsection discusses these menu options in detail. All options described in this section can be performed using the 5660 Silent Knight Software Suite (SKSS).

Important!

Before any customized programming is done, JumpStart should be run first. After JumpStart is run, thoroughly test the system. The reason the system should be tested after JumpStart is because Jumpstart automatically programs the system, searching for and configuring all SLC and SBUS devices it finds. JumpStart allows you to confirm the integrity of the installation prior to performing any custom programming. After determining that the hardware is properly installed, custom programming can be performed. Refer to Section 6.

7.1UL 864 Programming Requirements

NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER INVOLVED PARTIES: This product incorporates field programmable software. In order for the product to comply with the requirements in the Standard for Control Units and Accessories for Fire Alarm Systems, UL 864, certain programming features or options must be limited to specific values or not used at all as indicated below.

Programming Option

Menu Item

Permitted in

Possible

Settings Permitted in

UL 864 (Y/N)

Settings

UL 864

 

 

 

 

 

 

 

 

 

 

 

 

Phone Lines

Enable Gnd Start

No

Yes & No

No

 

 

 

 

 

Misc Options 1

Low AC Report Delay

Yes

0–30 hours

1–3

 

 

 

 

 

151209

7-1

Page 117
Image 117
Honeywell 5820XL manual Section Programming, UL 864 Programming Requirements