Section 7
Programming
This section of the manual describes how to manually program the control panel from the
Important!
Before any customized programming is done, JumpStart should be run first. After JumpStart is run, thoroughly test the system. The reason the system should be tested after JumpStart is because Jumpstart automatically programs the system, searching for and configuring all SLC and SBUS devices it finds. JumpStart allows you to confirm the integrity of the installation prior to performing any custom programming. After determining that the hardware is properly installed, custom programming can be performed. Refer to Section 6.
7.1UL 864 Programming Requirements
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER INVOLVED PARTIES: This product incorporates field programmable software. In order for the product to comply with the requirements in the Standard for Control Units and Accessories for Fire Alarm Systems, UL 864, certain programming features or options must be limited to specific values or not used at all as indicated below.
Programming Option | Menu Item | Permitted in | Possible | Settings Permitted in | |
UL 864 (Y/N) | Settings | UL 864 | |||
|
| ||||
|
|
|
|
| |
|
|
|
|
| |
Phone Lines | Enable Gnd Start | No | Yes & No | No | |
|
|
|
|
| |
Misc Options 1 | Low AC Report Delay | Yes | |||
|
|
|
|
|