Carrier 30XW150-400 specifications Touch Pilot Controller Identification Configuration Table

Models: 30XW150-400

1 148
Download 148 pages 52.93 Kb
Page 19
Image 19

Table 12 — Touch Pilot Controller Identification Configuration Table

CONTROLLER ID DATA

BLOCK NO.

VALUE AND RANGE

QUALIFIERS

Device Name

1

CHILLDSP

Default

8 character Name field

Optional

 

 

Local address

2

115

Default

Bus number

2

0

Default

Device (driver) type

2

0 = Non-bridge

Default

3 = Broadcast Acknowledger

Optional

 

 

Primary baud rate

3

38400

Default

Secondary baud rate

3

38400

Fixed

Device description

4

Global Chiller Display

Default

24 character text field

Optional

 

 

Device location

4

(Blank)

Default

24 character text field

Optional

 

 

Software part number

4

CESR-131363-01

Fixed

Model number

4

(Blank)

Fixed

Serial number

4

(Blank)

Fixed

Reference number

4

Version 1.0

Fixed

Broadcast address processing list (primary)

5

241-251, 254, 255 enabled

Defaults

241-255 enabled/disabled

Optional

 

 

Broadcast address processing list (secondary)

5

none

Not applicable

Table 13 — Touch Pilot™ User Configuration (USERCONF) Table

DESCRIPTION

LIMITS

UNITS

NAME

DEFAULT

Backlight always on?

No

 

BACKLITE

No

Yes

 

 

 

 

 

Full access password

0

 

PSWDFULL

3333

9999

 

 

 

 

 

Limited access password

0

 

PSWDLMTD

2222

9999

 

 

 

 

 

Active language

0

 

ACTLANG

0

1

 

 

 

 

 

Time format

0

 

TIMEFMT

0

1

 

 

 

 

 

Date format

0

 

DATEFMT

0

2

 

 

 

 

 

Units base

US

 

UNITBASE

US

Metric

 

 

 

 

 

Contrast control

Manual

 

CONTRAST

Auto

Auto

 

 

 

 

 

Network mode

0

 

NETWORK

0

1

 

 

 

 

 

Network settings

 

 

 

 

Alarm acknowledger

No

 

ALARMACK

No

Yes

 

 

 

 

 

Broadcast acknowledger

No

 

BROADACK

No

Yes

 

 

 

 

 

Equipment CCN address

 

 

 

 

Bus number

0

 

EQUIPBUS

0

239

 

 

 

 

 

Element number

1

 

EQUIPELE

1

239

 

 

 

 

 

Control variables

 

 

 

 

Equipment status (Not Used)

Name

 

EQSTATUS

NOT USED

char 8

 

 

 

 

 

Equipment start/stop (Not Used)

Name

 

STARSTOP

NOT USED

char 8

 

 

 

 

 

Alarm status (Not Used)

Name

 

ALSTATUS

NOT USED

char 8

 

 

 

 

 

Alarm reset (Not Used)

Name

 

ALRESET

NOT USED

char 8

 

 

 

 

 

BACKLIGHT ALWAYS ON? — This configuration is used to keep the backlight on continuously or to turn it off after 60 seconds with no activity.

Allowable Entries: No/Yes (No=0 or Yes=1)

Default Value:

No

FULL ACCESS PASSWORD — This configuration is used to specify the full access password. Refer to Table 1, Setup Menu, for additional information on passwords.

Allowable Entries: 0 through 9999

Default Value:

3333

19

Page 19
Image 19
Carrier 30XW150-400 Touch Pilot Controller Identification Configuration Table, Broadcast address processing list secondary