APPENDIX C — CCN TABLES (cont)

CONFIGURATION TABLES (cont)

TABLE

DISPLAY NAME

RANGE

DEFAULT

UNITS

POINT NAME

USER

Circuit Loading Sequence

0-3

0

 

lead_cir

 

 

0=Auto,

 

 

 

 

 

1=A Lead

 

 

 

 

 

2=B Lead,

 

 

 

 

 

3 =C Lead

 

 

 

 

Staged Loading Sequence

No/Yes

No

 

seq_typ

 

Ramp Loading Select

No/Yes

No

 

ramp_sel

 

Unit Off to On Delay

1-15

1

min

off_on_d

 

Condenser Pumps Sequence

0-4†

0

 

hpumpseq

 

Cooler Pumps Sequence

0-4

0

 

cpumpseq

 

 

0=No Pump

 

 

 

 

 

1=One Pump Only

 

 

 

 

 

2=Two Pumps Auto

 

 

 

 

 

3=Pump#1 Manual

 

 

 

 

 

4=Pump#2 Manual

 

 

 

 

Pump Auto Rotation Delay

24-3000

48

hours

pump_del

 

Pump Sticking Protection

No/Yes

No

 

pump_per

 

Stop Pump During Standby

No/Yes

No

 

pump_sby

 

Flow Checked if Pump Off

No/Yes

No

 

pump_loc

 

Auto Changeover Select*

No/Yes

No

 

auto_sel

 

Cooling Reset Select

0-4

0

 

cr_sel

 

Heating Reset Select*

0-4

0

 

hr_sel

 

 

1 =OAT*,

 

 

 

 

 

0=None

 

 

 

 

 

2=Delta T,

 

 

 

 

 

3=4-20mA Control

 

 

 

 

 

4=Space Temp

0

 

lim_sel

 

Demand Limit Type Select

0-2

 

 

 

0=None

 

 

 

 

 

1=Switch Control

 

 

 

 

 

2=4-20mA Control

 

 

 

 

mA For 100% Demand Limit

0-20

0

ma

lim_mx

 

mA For 0% Demand Limit

0-20

10

ma

lim_ze

 

Current Limit Select

No/Yes

No

 

curr_sel

 

Current Limit at 100%

0 to 2000

2000

amps

curr_ful

 

Heating OAT Threshold*

-4-32

5

°F

heat_th

 

Free Cooling Delta T Th*

14.4-27

18

°F

free_dt

 

Full Load Timeout

20-300

30

min

fc_tmout

 

HSM Both Command Select

No/Yes

No

 

both_sel

 

NIGHT CONTROL

 

 

 

 

 

Start Hour

00:00-24:00

00:00

 

nh_start

 

End Hour

00:00-24:00

00:00

 

nh_end

 

Capacity Limit

0-100

100

%

nh_limit

 

Ice Mode Enable

No/Yes

No

 

ice_cnfg

 

Reverse Alarms Relay

No/Yes

No

 

al_rever

 

Cooler pump off in heat

No/Yes

No

 

stopheat

 

Cond pump off in cool

No/Yes

No

 

stopcool

 

 

 

 

 

 

*Not supported.

†Only condenser pump sequence 1 is supported.

NOTES:

1.Flow checked if pump off needed when a command is sent to the primary pump to prevent cooler from freezing in winter conditions. Command will set the cooler flow switch to closed while the controls stop the cooler pump. The controls may then generate an alarm. If this decision is active, the cooler flow switch is not checked when the cooler pump is stopped.

2.If cooling reset select set point has been selected the set point based on 4-20mA input signal through ComfortLink™ control, then a 4-20 mA reset

function shall be ignored. Configuration 3 (4-20mA Control) and 4 (Space Temperature) shall require an Energy Management Module.

3.Configuration 2 (4-20mA Control) shall require an Energy Management Module. Configuration 1 Switch Demand limit provides 3 step demand limit if an Energy Management Module is present. Otherwise, only one step is allowed.

4.Reverse Alarms Relay configuration will be deenergized when an alarm and alert relay is present and will be energized when no alarm is present.

126