APPENDIX A — TOUCH PILOT™ DISPLAY TABLES (cont)

90

TOUCH PILOT DESCRIPTION

TOUCH PILOT

TOUCH PILOT PATH

LINE

READ/

CCN TABLE NAME

POINT NAME

WRITE

Current Setpoint

SP

MAIN MENU\Status\GENUNIT

31

RW

Status Display Tables\GENUNIT

Current Unoccupied Time

ENDTIME

MAIN MENU\Maint\OCCDEFCM\OCC1PO1S

6

RO

Maintenance Display Tables\OCCDEFCM\OCC1PO1S

Current Unoccupied Time

ENDTIME

MAIN MENU\Maint\OCCDEFCM\OCC2PO2S

6

RO

Maintenance Display Tables\OCCDEFCM\OCC2PO2S

Current Z Multiplier Val

zm

MAIN MENU\Maint\LOADFACT

18

RO

Maintenance Display Tables\LOADFACT

Customer Shutdown Out

Q_SHUT

MAIN MENU\Status\QCK_TST1

47

RW

Status Display Tables\QCK_TST1

Daylight Sav Ent Day of Week (1=Monday)

startdow

MAIN MENU\Config\BRODEFS

10

RW

Configuration Tables\BRODEFS\BROCASTS

Daylight Sav Ent Month

startmon

MAIN MENU\Config\BRODEFS

9

RW

Configuration Tables\BRODEFS\BROCASTS

Daylight Sav Ent Week of Month

startwom

MAIN MENU\Config\BRODEFS

11

RW

Configuration Tables\BRODEFS\BROCASTS

Daylight Sav Leaving Day of Week (1=Monday)

stopdow

MAIN MENU\Config\BRODEFS

14

RW

Configuration Tables\BRODEFS\BROCASTS

Daylight Sav Leaving Month

stopmon

MAIN MENU\Config\BRODEFS

13

RW

Configuration Tables\BRODEFS\BROCASTS

Daylight Sav Leaving Week of Month

stopwom

MAIN MENU\Config\BRODEFS

15

RW

Configuration Tables\BRODEFS\BROCASTS

Daylight Saving Select

dayl_sel

MAIN MENU\Config\BRODEFS

7

RW

Configuration Tables\BRODEFS\BROCASTS

Decription

DevDesc

MAIN MENU\Config\Ctlr-ID

1

RW

Configuration Tables\!CtlrID\PD5_XAXQ

Defrost Active On Cir A

Mode_19

MAIN MENU\Status\MODES

20

RO

Status Display Tables\MODES

Defrost Active On Cir B

Mode_20

MAIN MENU\Status\MODES

21

RO

Status Display Tables\MODES

Defrost Active?

 

 

 

 

 

Circuit A

mode[19]

MAIN MENU\Maint\DEFROSTM

4

RO

Maintenance Display Tables\DEFROSTM

Circuit B

mode[20]

MAIN MENU\Maint\DEFROSTM

21

RO

Maintenance Display Tables\DEFROSTM

Defrost Duration

 

 

 

 

 

Circuit A

defr_dua

MAIN MENU\Maint\DEFROSTM

6

RO

Maintenance Display Tables\DEFROSTM

Circuit B

defr_dub

MAIN MENU\Maint\DEFROSTM

23

RO

Maintenance Display Tables\DEFROSTM

Defrost Fan Offset Cal A

def_of_a

MAIN MENU\Maint\DEFROSTM

16

RO

Maintenance Display Tables\DEFROSTM

Defrost Fan Offset Cal B

def_of_b

MAIN MENU\Maint\DEFROSTM

33

RO

Maintenance Display Tables\DEFROSTM

Defrost Fan Start Cal A

def_ca_a

MAIN MENU\Maint\DEFROSTM

15

RO

Maintenance Display Tables\DEFROSTM

Defrost Fan Start Cal B

def_ca_b

MAIN MENU\Maint\DEFROSTM

32

RO

Maintenance Display Tables\DEFROSTM

Defrost Number

 

 

 

 

 

Circuit A

nb_def_a

MAIN MENU\Service\UPDHRFAN

6

RW

Service Configuration Tables\UPDHRFAN

Circuit B

nb_def_b

MAIN MENU\Service\UPDHRFAN

7

RW

Service Configuration Tables\UPDHRFAN

Defrost Number

 

 

 

 

 

Circuit A

nb_def_a

MAIN MENU\Status\FANHOURS

3

RO

Status Display Tables\FANHOURS

Circuit B

nb_def_b

MAIN MENU\Status\FANHOURS

4

RO

Status Display Tables\FANHOURS

Defrost Temperature

 

 

 

 

 

Circuit A

DEFRT_A

MAIN MENU\Maint\DEFROSTM

5

RO

Maintenance Display Tables\DEFROSTM

Circuit B

DEFRT_B

MAIN MENU\Maint\DEFROSTM

22

RO

Maintenance Display Tables\DEFROSTM

Delta - Reference Delta

 

 

 

 

 

Circuit A

delt_v_a

MAIN MENU\Maint\DEFROSTM

13

RO

Maintenance Display Tables\DEFROSTM

Circuit B

delt_v_b

MAIN MENU\Maint\DEFROSTM

30

RO

Maintenance Display Tables\DEFROSTM

Delta: OAT - Mean SST

 

 

 

 

 

Circuit A

delt_a

MAIN MENU\Maint\DEFROSTM

11

RO

Maintenance Display Tables\DEFROSTM

Circuit B

delt_b

MAIN MENU\Maint\DEFROSTM

28

RO

Maintenance Display Tables\DEFROSTM

Delta T Full Reset Value

dt_cr_fu

MAIN MENU\Setpoint\SETPOINT

8

RW

Setpoint Configuration Tables\SETPOINT

Delta T Full Reset Value

dt_hr_fu

MAIN MENU\Setpoint\SETPOINT

22

RW

Setpoint Configuration Tables\SETPOINT

Delta T No Reset Value

dt_cr_no

MAIN MENU\Setpoint\SETPOINT

7

RW

Setpoint Configuration Tables\SETPOINT

Delta T No Reset Value

dt_hr_no

MAIN MENU\Setpoint\SETPOINT

21

RW

Setpoint Configuration Tables\SETPOINT

Demand Limit Active

Mode_04

MAIN MENU\Status\MODES

5

RO

Status Display Tables\MODES

Demand Limit Type Select

lim_sel

MAIN MENU\Config\USER

24

RW

Configuration Tables\USER

Deri PID Gain Varifan

hd_dg

MAIN MENU\Service\SERVICE1

8

RW

Service Configuration Tables\SERVICE1

DGT Cool Solenoid

 

 

 

 

 

Circuit A

Q_CDGT_A

MAIN MENU\Status\QCK_TST1

21

RW

Status Display Tables\QCK_TST1

Circuit B

Q_CDGT_B

MAIN MENU\Status\QCK_TST1

28

RW

Status Display Tables\QCK_TST1

Circuit C

Q_CDGT_C

MAIN MENU\Status\QCK_TST1

9

RO

Status Display Tables\QCK_TST1

LEGEND

RO — Read Only

RW — Read/Write

Page 90
Image 90
Carrier 30XW150-400 Current Setpoint, Current Unoccupied Time, Current Z Multiplier Val, Customer Shutdown Out, Decription

30XW150-400 specifications

The Carrier 30XW150-400 series is a line of water-cooled chillers that exemplifies innovation, efficiency, and reliability in commercial cooling solutions. Designed for medium to large-scale applications, this series is ideal for a variety of settings, including commercial buildings, industrial processes, and chilled water systems.

One of the standout features of the Carrier 30XW series is its efficiency. The chillers utilize advanced variable-speed compressor technology, which allows the units to adapt to varying cooling loads while minimizing energy consumption. This technology not only reduces operational costs but also contributes to better environmental sustainability by lowering greenhouse gas emissions.

The 30XW series chillers are equipped with high-efficiency, scroll compressors that operate quietly and provide significant energy savings. By utilizing enhanced economizer controls, these units can achieve higher efficiency ratings, especially in part-load conditions. The result is an impressive Energy Efficiency Ratio (EER) and Seasonal Energy Efficiency Ratio (SEER), making these units a smart choice for energy-conscious businesses.

In terms of reliability, the Carrier 30XW150-400 series features robust construction and an array of safety and monitoring systems. The units come with advanced diagnostics that help in quickly identifying and addressing any operational issues. This proactive approach ensures reliability and minimizes downtime, which is crucial for maintaining optimal temperature controls in critical environments.

Additionally, the chillers incorporate environmentally friendly refrigerants that comply with the latest regulations, making them a sustainable choice for modern commercial applications. Their compact design allows for flexible installation options, and the integrated control systems provide the ability to optimize performance based on specific building management demands.

User-friendly interfaces and remote monitoring capabilities further enhance the ease of operation, allowing facility managers to have real-time insight into performance metrics and system health. This level of control contributes to better maintenance planning and maximizes the lifespan of the equipment.

In summary, the Carrier 30XW150-400 series of water-cooled chillers combines advanced technology, energy efficiency, and reliable performance, making it an ideal solution for various commercial and industrial cooling needs. With its commitment to innovation and sustainability, Carrier continues to set the standard in the HVAC industry.