Carrier 30XW150-400 specifications Record Configuration Information, CL-5

Models: 30XW150-400

1 148
Download 148 pages 52.93 Kb
Page 145
Image 145

Record Configuration Information

TOUCH PILOT™

NAVIGATOR

NAVIGATOR™

RANGE

DEFAULT

ENTRY

DESCRIPTION

ITEM

SUBMODE

 

 

 

Cooling Setpoint 1

CSP.1

Set PointCOOL

XXX.X

44.0° F

 

Cooling Setpoint 2

CSP.2

Set PointCOOL

XXX.X

44.0° F

 

Cooling Ice Setpoint

CSP.3

Set PointCOOL

XXX.X

44.0° F

 

Current No Reset Value (Cooling)

CRV1

Set PointCOOL

XXX.X

0

 

Current Full Reset Value (Cooling)

CRV2

Set PointCOOL

XXX.X

0

 

Delta T No Reset Value (Cooling)

CRT1

Set PointCOOL

XXX.X

0

 

Delta T Full Reset Value (Cooling)

CRT2

Set PointCOOL

XXX.X

0

 

OAT No Reset Value (Cooling)

CRO1

Set PointCOOL

XXX.X

14.0° F

 

OAT Full Reset Value (Cooling)

CRO2

Set PointCOOL

XXX.X

14.0° F

 

Space T No Reset Value

CRS1

Set PointCOOL

XXX.X

14.0° F

 

Space T Full Reset Value

CRS2

Set PointCOOL

XXX.X

14.0° F

 

Cooling Reset Deg. Value

DGRC

Set PointCOOL

XX.X

0

 

Cool Changeover Setpoint

CAUT

Set PointCOOL

XXX.X

75° F

 

Cooling Ramp Loading

CRMP

Set PointCOOL

X.X

1.0

 

Heating Setpoint 1

HSP.1

Set PointHEAT

XXX.X

100.0° F

 

Heating Setpoint 2

HSP.2

Set PointHEAT

XXX.X

100.0° F

 

Current No Reset Value (Heating)

HRV1

Set PointHEAT

XXX.X

0

 

Current Full Reset Value (Heating)

HRV2

Set PointHEAT

XXX.X

0

 

Delta T No Reset Value (Heating)

HRT1

Set PointHEAT

XXX.X

0

 

Delta T Full Reset Value (Heating)

HRT2

Set PointHEAT

XXX.X

0

 

OAT No Reset Value (Heating)

HRO1

Set PointHEAT

XXX.X

14.0° F

 

OAT Full Reset Value (Heating)

HRO2

Set PointHEAT

XXX.X

14.0° F

 

Heating Reset Deg. Value

DGRH

Set PointHEAT

XX.X

0

 

Heating Changeover Setpoint

HAUT

Set PointHEAT

XX.X

64.0° F

 

Heat Ramp Loading

HRMP

Set PointHEAT

X.X

1.0

 

Switch Limit Setpoint 1

DLS1

Set PointMISC

XXX

100

 

Switch Limit Setpoint 2

DLS2

Set PointMISC

XXX

100

 

Switch Limit Setpoint 3

DLS3

Set PointMISC

XXX

100

 

Water Val Condensing Stp

W.SCT

Set PointMISC

XXX.X

95.0° F

 

None (I/O Button)

OPER

Operating ModesSLCT

X

 

Setpoint Select

SP.SE

Operating ModesSLCT

X

 

 

 

 

 

 

 

Heal/Cool Select

HC.SE

Operating ModesSLCT

X

COOLING

 

 

 

 

 

 

 

*Not supported.

CL-5

Page 145
Image 145
Carrier 30XW150-400 specifications Record Configuration Information, CL-5